11 Troubleshooting
Event
Event, cause and corrective measures
number
6415
Self diagnosis / Interference device (6415)
The reference voltage test failed.
Corrective measures:
• Disconnect the Sunny Multigate from voltage sources (see Section 10, page 51)
and re-commission it (see Section 7, page 43).
• If this message is still displayed, contact the SMA Service Line.
6702
Interference device (6702)
The cause must be determined by the SMA Service Line.
Corrective measures:
• Contact the SMA Service Line.
7001
Fault sensor interior temperature (7001)
The temperature sensor for the indoor temperature of the Sunny Multigate is defective.
Feed-in operation will be interrupted.
Corrective measures:
• Contact the SMA Service Line.
7702
Self diagnosis / Interference device (7702)
An relay error has occurred.
Corrective measures:
• Disconnect the Sunny Multigate from voltage sources (see Section 10, page 51)
and re-commission it (see Section 7, page 43).
• If this message is still displayed, contact the SMA Service Line.
8101 to
Communication disturbed (8101, 8102)
8102
An error has occurred in the internal communication. This can be caused by one of the
following: Feed-in operation continues.
Corrective measures:
1. If several Sunny Multigate devices are installed in a PV system, check whether the
AC cabling of the inverters to the Sunny Multigate is laid separated from each
other. If the AC cables are not laid separately from each other, do lay the
AC cables from the inverter to the Sunny Multigate in separate locations.
2. If the problem persists, contact the SMA Service Line.
8104
Interference device (8104)
The cause must be determined by the SMA Service Line.
Corrective measures:
• Contact the SMA Service Line.