iNSTallaTiON
Electrical connection
f Route all power cables and sensor leads into the appliance
through the cable entry.
f Connect the power cables and sensor leads as detailed
below.
Install cables with the following cross-sections in accordance with
the respective fuse protection:
fuse protec-
assignment
tion
B 16 A
Control unit

11.1 Control voltage

Terminal
Control voltage
XD03.1
Power supply
L, N, PE

11.2 Safety extra low voltage

Termi-
Safety extra low voltage
nal
AA01-X1.1
Heat pump
AA01-X1.3
Outside sensor
AA01-X1.4 BT06 Temperature sensor, heat pump, buffer cylinder
www.stiebel-eltron.com
Cable cross-section
1.5 mm²
BT06
BT13
BT20
AA01-X1.6 BT13 Temperature sensor, heat pump, flow, heating circuit 2
(HSBC 3-HKM accessory)
AA01-X1.8 BT20 DHW cylinder temperature sensor
Control by WPM via PWM signal
f Observe the information in the commissioning instructions
for the WPM heat pump manager.

11.3 Heat pump manager terminal assignment

WARNING Electrocution
Only components that operate with safety extra low
voltage (SELV) and that ensure secure separation from
the mains voltage supply may be connected to the low
voltage terminals of the appliance.
Connecting other components can make parts of the ap-
pliance and connected components live.
f Only use components which have been approved by
us.
Safety extra low voltage
X1.1
+
+
CAN (connection for heat pump and WPE heat
CAN A
-
-
pump extension)
L
L
H
H
X1.2
+
+
CAN (connection for FET remote control and
CAN B
-
-
ISG Internet Service Gateway)
L
L
H
H
X1.3
Signal
1
Outside sensor
Earth
2
X1.4
Signal
1
Buffer sensor (heating circuit sensor 1)
Earth
2
X1.5
Signal
1
Flow sensor
Earth
2
X1.6
Signal
1
Heating circuit sensor 2
Earth
2
X1.7
Signal
1
Heating circuit sensor 3
Earth
2
X1.8
Signal
1
DHW cylinder sensor
Earth
2
X1.9
Signal
1
Source sensor
Earth
2
X1.10
Signal
1
2nd heat generator (2.WE)
Earth
2
X1.11
Signal
1
Cooling flow
Earth
2
X1.12
Signal
1
DHW circulation sensor
Earth
2
X1.13
Signal
1
FE7 remote control / telephone remote
Earth
2
switch / heating curve optimisation / SG Ready
Signal
3
HSBC 300 cool |
17