Heating Mode - Carrier 42QFD048D8S Service Manual

Table of Contents

Advertisement

3.4.4
Condenser Temperature Protection
When condenser temperature is more than setting value,
the compressor ceases operation..
3.4.5
Evaporator Temperature Protection
When evaporator temperature drops below a configured
value, the compressor and outdoor fan cease operation.
3.5
Heating Mode(Heat pump units)
3.5.1
Compressor Control
1) Reach the configured temperature
• If the following conditions are satisfied, the
compressor ceases operation.
• While calculated frequency(fb) is less than
minimum limit frequency(FminH).
• When protective time is more than or equal to ten
minutes.
• When T1 is higher than or equal to Tsc+
HDIFTEMP2.
Note: HDIFTEMP2 is EEPROM setting parameter. It is 2°C
usually.
• If one of the following conditions is satisfied, not
judge protective time.
• Compressor running frequency is more than test
frequency.
• When compressor running frequency is equal to
test frequency, T4 is higher than 15°C or T4 sensor
fault.
• Change setting temperature.
• Turbo function on/off.
2) When the current is higher than the predefined safe
value, surge protection is activated, causing the
compressor to cease operation.
3.5.2
Indoor Fan Control:
• When the compressor is on, the indoor fan speed can
be set to high, (medium) ,low, or auto. And the anti-
cold wind function has the priority.
• Anti-cold air function
• The indoor fan is controlled by the indoor unit coil
temperature T2.
• Auto fan action in heating mode:
3.5.3
Case 1:
• The outdoor unit will be run at different fan speed
according to T4 and compressor frequency.
• For different outdoor units, the fan speeds are
different.
Case 2:
• The outdoor unit will be run at different fan speed
according to T4.
• For different outdoor units, the fan speeds are
different.
3.5.4
• The unit enters defrosting mode according to the
temperature value of T3 and T4 as well as the
compressor running time.
• In defrosting mode, the compressor continues to run,
the indoor and outdoor motor will cease operation,
the defrost light of the indoor unit will turn on, and
the "
• If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal

heating mode:

• T3 rises above TCDE1.
Product Features
Outdoor Fan Control:
Defrosting mode
" symbol is displayed.
5