TS06-INV: Refrigerant Leakage Detection diagnosis and solution
For some models,
Description: Define the evaporator coil temperature T2 of the compressor just starts running as Tcool.
In the beginning 5 minutes after the compressor starts up, if T2 < Tcool-1°C(1.8°F) does not keep continuous 4 seconds
and compressor running frequency higher than 50Hz does not keep for 3 minutes, and this situation happens 3 times,
the LED displays the failure code and the AC turns off.
Recommended parts to prepare:
• T2 sensor
•
Indoor PCB
• Additional refrigerant
Troubleshooting and
Power off, then restart the unit 2 minutes later.
Does a problem remain?
Put your hands in front of the
air blowing out from
Check system for leakages.
Check System for blockages and
clear blockages if present.
repair:
YES
indoor air outlet.
Is there cool
indoor air outlet?
NO
NO
Are any leakages
present?
NO
Check the T2 sensor.
YES
Repair the leakage and
YES
recharge the refrigerant.
Troubleshooting
Is it securely
YES
attached?
Replace the
indoor PCB