17. Remove the pressure switch bracket assembly.
18. Remove the screw that holds PS2, rotate 90 degrees
clockwise, and reattach.
19. Reattach the pressure switch bracket assembly.
N N o o t t e e : : The inducer is shown rotated into its final
position in the illustration below.
20. Cut 3" hole in bottom panel using large dimple as
guide.
21. Attach the vent outlet gasket to the vent outlet.
22. Install vent outlet to top of cabinet using 2 screws
supplied in the doc pack.
23. Install vent inlet gasket and vent inlet using 4
screws supplied in the doc pack.
N N o o t t e e : : The vent outlet adapter is used for strain relief
against the weight of the venting. The clamp
should be tightened after the internal connection
is made.
S9V2-VS-SVX001-1B-EN
F F u u r r n n a a c c e e C C o o m m b b u u s s t t i i o o n n A A i i r r E E x x h h a a u u s s t t O O p p t t i i o o n n s s
N N o o t t e e : : If required, transition to larger venting within 2'
of the cabinet. An 2" x 3" offset coupling is
required if the transition is made in a horizontal
plane. Use coupling CPL00938 (Canadian
applications may use BAYREDUCE to meet ULC-
S636 requirements.) See Horizontal Venting
section for proper orientation of 2" x 3" offset
coupling.
24. Slide PVC through vent outlet adaptor and insert
into inducer outlet.
25. Twist to insure PVC is fully inserted.
26. Tighten the two clamps.
27. Install the combustion air inlet PVC pipe.
Condensate Trap Installation
28. Reinstall the condensate adapter if it was earlier
removed or ensure adapter is still in place.
I I m m p p o o r r t t a a n n t t : : The condensate adapter must be present
for proper condensate drain operation.
83