*1: AD indicator: If the indicator blinks, it means that AD/DA conversion is being executed.
*2: ALARM indicator: If the indicator blinks, it means that the AD/DA conversion value exceeds the range which
can be used.
*3: Installing a battery: Users have to replace the battery in the PLC in three minutes. Please refer to section 3.2
for more information.
Electrical Specifications
Electrical Specifications
Model
Item
Power supply voltage
Fuse
Power Consumption
Insulation Resistance
Noise Immunity
Grounding
Environment
Vibration / Shock
Resistance
Weight (approx.) (g)
Approvals
Electrical Specification of Input Point
Input Type
DC (SINK or SOURCE)
Input Current 24VDC 5mA
Off → On,
X0,X1: above 18.5VDC
X2,X3: above 16.5VDC
Active Level
On→Off,
X0~X3 below 8VDC
About 10ms (An
Responding
adjustment range of 0 ~ 20
Time
ms could be selected
through D1020 and D1021)
Model Name & I/O Configuration
Model
Power
DVP10SX11R
24VDC
+20%
DVP10SX11T
-15%
Installation & Wiring
3.1 PLC Mounting Arrangements and Wiring Notes
DVP10SX11R/T
DVP08SM11N
CPU: 24VDC (-15% ~ 20%) (with DC input reverse polarity protection),
Expansion Unit: supplied by the CPU
2A / 250VAC
5W
> 5 MΩ at 500 VDC (Between all inputs / outputs and earth)
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz~1GHz, 10V/m
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N
(All DVP units should be grounded directly to the ground pole).
Operation: 0°C ~ 55°C (temperature), 5 ~ 95% (humidity), Pollution degree 2;
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity); D/A output operation: 0°C ~ 50°C
(temperature)
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
138 / 133
Output Type Relay-R
Current
Specification
Voltage
Specification
Maximum
Loading
Responding
Time
Input
Point
DI AI
DI
4
2 DC24V/5mA
Sink or
4
2
Source
DVP08SN11R/T
1W
1.5W
64
88 / 68
Electrical Specification of Output Point
1.5A/1 point
0.3A/1 point @ 40°C; When the output of Y0 and
(5A/COM)
Y1 is high-speed pulse, Y0 and Y1 = 30mA
Below
250VAC,
30VDC
30VDC
75VA
(Inductive)
9W/1 point
90 W
(Resistive)
About 10
Off→On 20us
ms
On→Off 30us
Type
AI
-20 ~ 20mA
range(-1,000 ~ +1,000)
-10 ~ +10V
range(-2,000 ~ +2,000)
DVP08SP11R/T
-
1.5W
90 / 70
Transistor-T
When the output of Y0 and Y1
is high-speed pulse, Y0 and
Y1 = 0.9W (Y0 = 32kHz, Y1 =
10kHz)
Y0 and Y1 are specified points
for high-speed pulse
Output
Point
DO AO
DO
2
2
Relay
(range:-2,000 ~ +2,000)
2
2
Resistor
(range:-2,000 ~ +2,000)
DVP16SP11R/T
2W
96 / 76
Type
AO
-20 ~ 20mA
-10 ~ +10V