Electrical Specifications; Installation And Wiring - Delta DVP-SX Instruction Sheet

Multi-functional, built-in analog i/o, multiple instructions

Advertisement

Available languages

Available languages

*1: AD indicator: If the indicator blinks, it means that AD/DA conversion is being executed.
*2: ALARM indicator: If the indicator blinks, it means that the AD/DA conversion value exceeds the range which
can be used.
*3: Installing a battery: Users have to replace the battery in the PLC in three minutes. Please refer to section 3.2
for more information.
 Electrical Specifications
 Electrical Specifications
Model
Item
Power supply voltage
Fuse
Power Consumption
Insulation Resistance
Noise Immunity
Grounding
Environment
Vibration / Shock
Resistance
Weight (approx.) (g)
Approvals
Electrical Specification of Input Point
Input Type
DC (SINK or SOURCE)
Input Current 24VDC 5mA
Off → On,
X0,X1: above 18.5VDC
X2,X3: above 16.5VDC
Active Level
On→Off,
X0~X3 below 8VDC
About 10ms (An
Responding
adjustment range of 0 ~ 20
Time
ms could be selected
through D1020 and D1021)
 Model Name & I/O Configuration
Model
Power
DVP10SX11R
24VDC
+20%
DVP10SX11T
-15%
 Installation & Wiring
3.1 PLC Mounting Arrangements and Wiring Notes
DVP10SX11R/T
DVP08SM11N
CPU: 24VDC (-15% ~ 20%) (with DC input reverse polarity protection),
Expansion Unit: supplied by the CPU
2A / 250VAC
5W
> 5 MΩ at 500 VDC (Between all inputs / outputs and earth)
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz~1GHz, 10V/m
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N
(All DVP units should be grounded directly to the ground pole).
Operation: 0°C ~ 55°C (temperature), 5 ~ 95% (humidity), Pollution degree 2;
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity); D/A output operation: 0°C ~ 50°C
(temperature)
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
138 / 133
Output Type Relay-R
Current
Specification
Voltage
Specification
Maximum
Loading
Responding
Time
Input
Point
DI AI
DI
4
2 DC24V/5mA
Sink or
4
2
Source
DVP08SN11R/T
1W
1.5W
64
88 / 68
Electrical Specification of Output Point
1.5A/1 point
0.3A/1 point @ 40°C; When the output of Y0 and
(5A/COM)
Y1 is high-speed pulse, Y0 and Y1 = 30mA
Below
250VAC,
30VDC
30VDC
75VA
(Inductive)
9W/1 point
90 W
(Resistive)
About 10
Off→On 20us
ms
On→Off 30us
Type
AI
-20 ~ 20mA
range(-1,000 ~ +1,000)
-10 ~ +10V
range(-2,000 ~ +2,000)
DVP08SP11R/T
-
1.5W
90 / 70
Transistor-T
When the output of Y0 and Y1
is high-speed pulse, Y0 and
Y1 = 0.9W (Y0 = 32kHz, Y1 =
10kHz)
Y0 and Y1 are specified points
for high-speed pulse
Output
Point
DO AO
DO
2
2
Relay
(range:-2,000 ~ +2,000)
2
2
Resistor
(range:-2,000 ~ +2,000)
DVP16SP11R/T
2W
96 / 76
Type
AO
-20 ~ 20mA
-10 ~ +10V