ENGLISH Thank you for choosing Delta’s DVP series PLC. DVP02DA-E2 (DVP04DA-E2) analog output module receives 2 (4) groups of 16-bit digital data from the PLC MPU and converts the digital data into 2 (4) points analog output signals (voltage or current). In...
Control Register Attrib. Register name Explanation Set up by the system, model code: Model name DVP02DA-E2 = H’0041; DVP04DA-E2 = H’0081 Firmware version Display the current firmware version in hex. Output mode: Default = H’0000. O R/W CH1 output mode setting Take CH1 for example: Mode 0 (H’0000): Voltage output ( 10V)
Page 5
Attrib. Register name Explanation O R/W Adjusted Gain value of CH1 Set the adjusted Gain value of CH1 ~ CH4. Default = K16,000. O R/W Adjusted Gain value of CH2 Definition of Gain: O R/W Adjusted Gain value of CH3 The corresponding voltage (current) input O R/W Adjusted Gain value of CH4 value when the digital output value = 16,000...
Page 6
When DVP-ES2 MPU is connected with modules, registers D9900~D9999 will be reserved for storing values from modules. You can apply MOV instruction to operate values in D9900~D9999. When ES2 MPU is connected with DVP02DA-E2/DVP04DA-E2, the configuration of special registers is as below: Module...
Page 7
Mode 0 (CR#2 ~ CR#5) -10V ~ +10V Gain = 5V (16,000) Offset = 0V (0) Range of digital data -32,000 ~ +32,000 Max./Min. range of digital data -32,768 ~ +32,767 Current output – mode 1: 20mA Gain Current output 10mA +32767 +16000...