Model Explanation & Peripherals Thank you for choosing Delta DVP series PLC. DVP06XA-H2 is able to receive 4 points of analog input signals (voltage or current) and convert them into 12-bit digital signals. DVP06XA-H2 receives 2 groups of 12-bit digital data from PLC MPU and converts them into 2 points of analog signal for output (in voltage/current).
0.1~0.47 μF and 25 V capacitor. *6: Please connect the terminal on both the A C m otor drive power module and DVP06XA-H2 to the system Recorder Shielded cable *4 Scale valve... earth point and ground the system contact or...
Register content b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 address Set up by the system. DVP06XA-H2 model code = H’6604 H’40C8 Model name You can read the model name from the program and see if the ○...
Page 5
RS-485 parameter Latched Register content b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 address H’40E1 R/W Adjusted GAIN value of CH2 When voltage input, range: K-800 ~ K4,000. ○ When current input, range: K-800 ~ K2,600. H’40E2 R/W Adjusted GAIN value of CH3 ○...
Page 6
- Firmware V4.04 (and lower): Data format (b11~b8) is not available, ASCII format is 7, E, 1 (code H’00xx), RTU format is 8, E, 1 (code H’C0xx/H’80xx). - Firmware V4.05 (and higher): Refer to the following table for setup. For new communication format, please take note that modules in the original code H’C0xx/H’80xx is changed to 8E1 for RTU.
Page 7
GAIN - OFFSET Range: +400 ~ +6,000 CR#1 mode 2 GAIN = 12mA (2,400 ). OFFSET = 4mA (800 Current output CR#1 mode 3 GAIN = 10mA (2,000 ). OFFSET = 0mA (0 20mA Mode 2 The current output value when digital input value = GAIN K2,000.