Unit ratings

The following tables provide the maximum motor FLC that should be used on each SS6000 model for specific
starting & operating duties.
15A – 80A with Integral Bypass Contactor (
Standard
Light Duty:
Duty:
15A
15A
30A
25A
60A
54A
80A
70A
220 -460V 3 Wire Bypass
Light Duty:
Standard Duty:
105
193
170
221
193
367
321
586
513
830
806
220 -460V 3 Wire Continuous
Light Duty:
Standard Duty:
100
178
157
203
179
341
302
534
473
796
710
220 -460V 6 Wire Bypass (inside Delta Connection)
Light Duty:
Standard Duty:
180
159
330
290
380
330
635
555
1015
888
1435
1395
Technical Manual: Smartstart
Severe Duty:
15A
20A
44A
56A
Severe Duty:
92
82
151
172
285
456
716
Severe Duty:
88
78
141
161
270
425
641
Severe
Duty:
140
260
295
490
789
1240
®
6000
Page 30
380 - 415V)
Model
Chassis
6R015B2
B2
6R030B2
B2
6R060B2
B3
6R080B2
B3
Model
Chassis
6R10000
A2
6R19000
A2
6R22000
A2
6R36000
A3
6R58000
A3
6R83000
A3
Model
Chassis
6R10000
A2
6R19000
A2
6R22000
A2
6R36000
A3
6R58000
A3
6R83000
A3
Model
Chassis
6R10000
A2
6R19000
A2
6R22000
A2
6R36000
A3
6R58000
A3
6R83000
A3
Dimensions (mm)
335h 162w 174d
335h 162w 174d
440h 162w 174d
440h 162w 174d
Dimensions (mm)
430h 248w 232d
430h 248w 232d
430h 248w 232d
670h 375w 285d
670h 375w 285d
670h 375w 285d
Dimensions (mm)
430h 248w 232d
430h 248w 232d
430h 248w 232d
670h 375w 285d
670h 375w 285d
670h 375w 285d
Dimensions
(mm)
430h 248w 232d
430h 248w 232d
430h 248w 232d
670h 375w 285d
670h 375w 285d
670h 375w 285d
IMI0042 rev D

Advertisement

Table of Contents
loading

Table of Contents