Setup Menu - Protection - Zener SMARTSTART 6000 Series User Manual

Table of Contents

Advertisement

Programming
C13 Final Torque: (torque control only)
This sets the torque provided at the end of the
acceleration period. This is entered as a
percentage of nominal Torque (FLT).
Range:
15 to 200%
Default:
130%
To save changes
To exit without saving
C20 Decel Ramp:
C20 Decel Ramp
Start Torque
Final Torque
To enter submenu to modify
To exit sub menu
C21 Decel Time:
The time taken to decelerate the motor to the
'release torque setting'.
Range:
0 to 120 seconds
Default:
0 s
To save changes
To exit without saving
C22 Release Torq:
The Smartstart 6000 will decelerate the motor at
the 'decel time' rate until the torque reaches the
release torque value entered. This is entered as
a percentage of nominal Torque (FLT).
Range:
0 to 100%
Default:
2%
To save changes
To exit without saving
In pump applications the deceleration provided by the
Smartstart 6000 will reduce problems with water
hammer with greater control of the motor torque &
speed. The Smartstart 6000 has advanced settings to
customise the control of the motor during acceleration
and deceleration. Refer to Menu 'Advanced Controls'
on page 25 for more details.
Technical Manual: Smartstart
0
%
®
6000
Setup Menu
4 Protection
P01 Mtr Overload:
The Smartstart 6000 continuously monitors the
motor current (even in bypass) and calculates the
temperature rise of the motor. The tripping curves
are based on the protection classes as defined by
IEC60947-4-2. Refer to page 29 for more details
on overload class curves. Select the overload
protection class suitable for the motor & load
combination. This protection is type R1, thus will
not reset the thermal capacity when power is
removed or motor is stopped. This prevents the
motor from restarting if the motor is too hot.
Range:
Default:
To save changes
To exit without saving
The overload setting must be selected according
to the motor manufacturers recommendations.
P02 Mtr OverTemp:
Provides overload protection of the motor by
monitoring the actual motor temperature. A
thermistor or NC switch can be connected directly
to terminals 20 and 21. This will operate in
conjunction with P02 Mtr Therm OL.
Range:
Default:
To save changes
To exit without saving
PTC type:
i. Trip resistance 3000 ohms
ii. Reset 1650 ohms
iii. Thermistor Fault <20ohms
P03 Ph Rotation:
Selectable phase sequence protection to inhibit
motor operation if a prohibited phase sequence is
detected such as reverse operation. Ideal for
pumping applications.
Range:
Default:
To save changes
To exit without saving
Page 18
2;10a;10;15;20;25;30;disabled
10
Thermistor; NC switch; disabled
NC switch
Ignore; 1-2-3; 3-2-1;
Ignore
IMI0042 rev D