Programming
Setup Menu
9 Commands
To clear/reset any of the following a confirmation
code is required:
1
Reset Trip
2
Clr Mtr OL
3
Clr Counters
4
Clr Meters
5
Reset Config
11 Clr Stress
12 Clr All Data
13 Factory Reset
The Confirmation Code is: 1470
Technical Manual: Smartstart
®
6000
Setup Menu
10 Starter Diag
This menu provides indication of inputs and wiring
checks.
Each Relay can also be forced on and the Analogue
output set for 100%.
S1 Digital In:
Enable Input
Digital 1 Input
Digital 2 Input
0 = No control signal present
1 = Control signal present
S2 Thermistor In:
Displays thermistor resistance in Kohms.
The trip resistance is 3000Ohms and a short circuit is
detected when <20Ohms.
S3 Chk Motor Wirirng:
Displays detected motor wiring.
Example: ' Correct
S4 Chk CT1/CT2
Displays detected CT connection.
Example: 'Correct
Page 25
S1 Digital In
EN=0
D1=0
D2=0
Mtr 3 wire '
+L1 / +L3'
IMI0042 rev D