Step
Checking
5
5-1. Walk test
5-2. System check
Check the image at the time of detection on the monitoring portal.
1
Turn LED back ON, if it was turned OFF (
2
Close the PIR cover.
Walk around the detection area to make sure it is set as intended.
3
If necessary, turn LED OFF again.
4
Fix the PIR cover with the cover lock screw after completion.
5
NOTE
For the walk test, walk at least 1.0 m (3'3") away from the detector.
Conduct a walk test at least once a year.
13
DIP switch No. 1
, Default ON).