Mounting The Switch On A Workbench; Grounding The Switch; Grounding The Switch With A Grounding Strip - HP A5820X Series Installation Manual

Hide thumbs Also See for A5820X Series:
Table of Contents

Advertisement

Mounting the switch on a workbench

IMPORTANT:
Ensure good ventilation and 10 cm (3.9 in) of clearance around the chassis for heat dissipation.
Avoid placing heavy objects on the switch.
To mount a switch (except the A5800AF-48G and the A5820AF-24XG) on a workbench:
Check that the workbench is sturdy and well grounded.
1.
Place the switch with bottom up, and clean the round holes in the chassis bottom with dry cloth.
2.
Attach the rubber feet to the four round holes in the chassis bottom.
3.
Place the switch with upside up on the workbench.
4.

Grounding the switch

WARNING!
Correctly connecting the switch grounding cable is crucial to lightning protection and EMI protection.
The power input end of the switch has a noise filter, whose central ground is directly connected to the
chassis to form the chassis ground (commonly known as PGND). You must securely connect this chassis
ground to the earth so the faradism and leakage electricity can be safely released to the earth to
minimize EMI susceptibility of the switch.
You can ground a switch by using a grounding strip at the installation site or the AC power cord
connected to the switch.
NOTE:
The power and grounding terminals in this section are for illustration only.

Grounding the switch with a grounding strip

WARNING!
Connect the grounding cable to the grounding system in the equipment room. Do not connect it to a fire
main or lightning rod.
If a grounding strip is available at the installation site, connect the grounding cable to the grounding
strip.
17