cULus Hazardous (Classified) Locations
Underwriters Laboratories, Inc.: cULus IND. CONT. EQ. FOR HAZ. LOC.
Applied standards:
• ANSI ISA 12.12.01
• CSA C22.2 No. 213-M1987
APPROVED for Use in:
• Cl. 1, Div. 2, GP. A, B, C, D T4A; Ta = -20 °C...60 °C
• Cl. 1, Zone 2, GP. IIC T4; Ta = -20 °C...60 °C
Report / UL file: E223122 (NRAG7.E223122)
Note the conditions for the safe deployment of the product according to the section Notes on
use in hazardous areas according to UL HazLoc and FM (Page 24).
FM
Factory Mutual Approval Standard Class Number 3600, 3611, 3810, ANSI/ISA-61010-1
Equipment rating:
Class I, Division 2, Group A, B, C, D, Temperature Class T4A, Ta = 60 °C
Class I, Zone 2, Group IIC, Temperature Class T4, Ta = 60 °C
(Ta reduced to 50 ºC when mounted vertically)
Report Number: 3040919
Observe the conditions for safe usage of the CP according to the section Notes on use in
hazardous areas according to UL HazLoc and FM (Page 24).
Australia - RCM
The CP meets the requirements of the AS/NZS 2064 standards (Class A).
EAC (Eurasian Conformity)
Customs union of Russia, Belarus and Kazakhstan
Declaration of conformity according to the technical regulations of the customs union
(TR CU)
MSIP 요구사항 - For Korea only
A급 기기(업무용 방송통신기자재)
이 기기는 업무용(A급) 전자파 적합기기로서 판매자 또는 사용자는 이 점을 주의하시기
바라며, 가정 외의 지역에서 사용하는것을 목적으로 합니다.
Note that in terms of the emission of interference, this device corresponds to limit class A.
This device can be used in all areas except for residential environments.
SIMATIC CM 1243-5
Operating Instructions, 01/2023, C79000-G8976-C246-06
Approvals
51