Position For Outdoor Unit; Tubing Selection - Beko BRAE 090 User Manual

Table of Contents

Advertisement

Available languages

Available languages

7
Installation manual
7.4

Position for outdoor unit

• Avoid direct sunlight.
• Away from heat source, steam source,
leakage of flammable gas, smoke and dust.
• Select a place that is away from rain (snow)
and has good ventilation.
• Neighbors will not be affected by the blown
wind and noise, or discharged water.
• The place that is easy to install and service.
7.5

Tubing selection

• Ensure that the level (height) difference of
indoor and outdoor units and the length of
tubing meet the requirement In the Table 1.
• If the tubing is longer than 7m, but shorter
than 15m, refrigerant should be supplemented
according to Table 1.
• If the installation position of the outdoor unit is
higher than indoor unit and the tubing is longer
than 10m, added a oil trap on the gas tubing
for every 8m. (Fig.3)
30 / 46 EN
• Mounted on the solid and reliable foundation
will not increase noise or shock.
• To get high cooling performance, make sure
the unit's front, rear, left and right sides must
be located in an open area.
• The outlet is proposed to be in open air, any
obstacle will affect the performances.
• The installing distance must be required as
Fig. 2 shows.
At least 10cm
At least
15cm
At least 2m
Fig. 2
Split Type Air Conditioner / User Manual
At least
40cm