Panduit PViQ Switched POU User Manual Switched and Environmental Monitored Switched with Per Outlet Power and Environmental Monitored MN028 Version 2.0...
No software other than a web browser is required for operation and several data formats are available. In the PViQ Switched series, built-in sensors monitor Voltage, Current, instantaneous and cumulative Power, as well as calculated Power Factor.
PViQ Switched POU Networking Protocols HTTP, HTTPS (SSL/TLS), SMTP, POP3, ICMP, DHCP, TCP/IP, NTP, Telnet, Syslog Ethernet Link Speed 10/100 Mbit; full-duplex Data Formats HTML, SNMP, CSV/Plain Text, XML EMC Verification This Class A device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
PViQ Switched POU Installation Guidelines If the POU is installed in a cabinet the ambient temperature should be no greater than 40°C. Install the POU such that the amount of airflow required for safe operation of equipment is not compromised.
PViQ Switched POU Mounting "L" Bracket Affix Power Strip Mounting mounting brackets using #12-24 screws provided into tapped holes in the front or the sides of the post. Power Strip Mounting Brackets can also be mounted to the rear equipment rails.
PViQ Switched POU Toolless Mounting Hardware Use toolless buttons with key-holed slots built into cabinet or with optional key-holed brackets. Version 1.0...
Page 10
PViQ Switched POU Panduit Cabinet CS3 Version 1.0...
Default IP Address The PViQ Switched units have a default IP address for initial setup and access to the unit if the assigned address is lost or forgotten. Once an IP address is assigned to a unit, the default IP address is no longer active.
Page 12
PViQ Switched POU Typical Network Card Settings for PC or Laptop to connect to default IP address Version 1.0...
PViQ Switched POU Web Interface Overview The unit is accessible via a standard, unencrypted HTTP connection as well as an encrypted HTTPS (SSL) connection. The following web pages are available: Sensors Page The front page, Sensors, gives both instantaneous and historical views of the unit’s data. Real time readings are provided for all power strip data, outlet group data, and sensor data next to historical graphs.
PViQ Switched POU Logging Page The Logging page allows the user to access the historical data by selecting the desired sensors and time range to be logged. Checked readings in the Sensor Measurement Data Graph section are graphed on the Logging page and displayed on the optional remote display module. Checked readings in the Logged Measurements section are logged into the data file at a rate of one point per minute and will be available for graphing and display.
PViQ Switched POU Display Page The Display page allows the user to assign friendly names to attached sensors as well as change the default temperature unit of measure for external sensors. The display page also allows the user to select between the default and classic web page layouts.
PViQ Switched POU Alarms Page The Alarms page allows the user to establish alarm conditions for each sensor reading. Alarm conditions can be established with either high or low trip thresholds. The alarms are displayed in different sections based on the device the alarm is associated with. Alarm options include a local Buzzer, Email and SNMP Trap.
PViQ Switched POU Control Page The Control page has two sub-tabs; Actions and Settings. See Remote Outlet Switching for details. Control Actions Tab The Actions tab on the Control page gives the user control of the outlets. Outlets can be rebooted or turned on/off with or without pre-programmed delays.
PViQ Switched POU Control Settings Tab The Settings tab on the Control page allows the user to name and define a URL for outlets in addition to setting time delays for each outlet action. Boot up status and sequential boot up options are also available.
PViQ Switched POU Configuration Page The Configuration page has five sub-tabs; Network, Monitoring, Diagnostics, Event Log, and Admin. See Unit Configuration for details. Configuration Network Tab The user can enter and update the network settings on the Network tab of the Configuration page. See Unit Configuration section for details.