Diagnostic Leds; Fig. 31 Diagnostic Leds - Beckhoff EP1957-0022 Operating Instructions Manual

Twinsafe ethercat box with 8 fail-safe inputs and 4 fail-safe outputs
Table of Contents

Advertisement

Operation
5.5.3

Diagnostic LEDs

Fig. 31: Diagnostic LEDs
LED displays
LED
lit
DIA1
Environment variables,
(green
operating voltage and
)
internal tests are in the
valid range
• If DIA2 flashes, a
logic error code
applies
DIA2
Together with DIA3 and
(red)
4:
Global Shutdown
occurred. (see diag
history of the TwinSAFE
components)
DIA3
Global Fault or Global
(red)
Shutdown on µC1
DIA4
Global Fault or Global
(red)
Shutdown on µC2
1. A global fault permanently disables the TwinSAFE component, so that it has to be replaced. A global
shutdown temporarily disables the TwinSAFE component. The error can be reset by switching off and
back on again.
Logic error codes of LED DIA2 (if LED DIA1 is lit)
Flashing
Description
Code
1
Function block error in one of the TwinSAFE groups
2
Communication error in one of the TwinSAFE groups
3
Error combination: function block and communication
4
General error in one of the TwinSAFE groups
5
Error combination: general and function block
6
Error combination: general and communication
7
Error combination: general, function block and communication
48
flashes
-
Logic or environment error
code according to DIA1
1)
has
and tables below is output
-
1)
-
1)
Version: 2.0.0
flickering
off
Environment variables,
operating voltage and
internal tests are outside
the valid range
• If DIA2 flashes, an
environment error code
applies
Fault in a safe
Together with DIA3 and 4:
input or output
Global Fault
module
occurred. (see diag history
of the TwinSAFE
components)
No Global Fault or Global
Shutdown on µC1
No Global Fault or Global
Shutdown on µC2
EP1957-0022 and EP1957-2222
1)
has
1)
1)