Fig. 25 Safety Parameter Tab - Beckhoff EP1957-0022 Operating Instructions Manual

Twinsafe ethercat box with 8 fail-safe inputs and 4 fail-safe outputs
Table of Contents

Advertisement

Fig. 25: Safety Parameter tab
Index
Name
8000:01
ModuloDiagTestPulse
(FSOUT Module 1)
8000:02
MultiplierDiagTestPulse
(FSOUT Module 1)
8000:03
Standard Outputs active
(FSOUT Module 1)
8000:04
Diag TestPulse active
(FSOUT Module 1)
8000:07
Module Fault Link active
8010:01-04 Parameters for FSOUT
module 2
8020:01-04 Parameters for FSOUT
module 3
8030:01-04 Parameters for FSOUT
module 4
8040:01
ModuloDiagTestPulse
(FSIN Module 1)
8040:02
MultiplierDiagTestPulse
(FSIN Module 1)
8040:04
Diag TestPulse active
(FSIN Module 1)
EP1957-0022 and EP1957-2222
Default value/
Description
unit
0x00 / integer
Modulo value for the frequency of the generation of a test pulse.
0 -> every time
1 -> every second time
and so on
0x01 / integer
Length of the test pulse in multiples of 400 µs
FALSE / Boolean Activation of the logical AND operator of the safe and standard outputs
of the module
TRUE / Boolean
Activation of test pulses for the corresponding output module
TRUE / Boolean
If a module error occurs in this module, a module error is also set for
all other output modules of this TwinSAFE component for which this
parameter is also set to TRUE.
see module 1
see module 1
see module 1
see module 1
see module 1
see module 1
0x00 / integer
Modulo value for the frequency of the generation of a test pulse.
0 -> every time
1 -> every second time
and so on
0x01 / integer
Length of the test pulse in multiples of 400 µs
TRUE / Boolean
Activation of test pulses for the corresponding input module
Version: 2.0.0