Residual Current Device (RCD)
A Residual Current Device is integrated in the
Charging Robot.
The RCD will break the current in case a residual
current exceeding 6mA DC or 30mA AC is detected.
Disconnection time is according to EN 61008-1 and
IEC 62955.
The RCD is automatically tested between each
charging session or at least every 24h.
For manual initialization of the RCD-test, please
refer to the Installer App.
The integrated RCD has no influence on the function
of external protective devices.
An external RCD is required when at least one of the
below conditions are identified:
• The installation, including cable, junction boxes
etc., includes components with only basic
insulation (Class I).
• Any other electrical equipment apart from Easee
Home/Charge, including lamps and socket outlets,
is connected to the circuit.
• Any other conditions identified by the authorized
installer requiring an external RCD.
The internal RCD is considered to provide the
required RCD protection for both AC and DC leakage
faults when all the below conditions are fulfilled:
• The installation, including cable, junction boxes
etc, is performed entirely with components
providing double or reinforced insulation (Class II).
• No other electrical equipment apart from Easee
Home/Charge, including lamps and socket outlets,
is connected to the circuit.
• No other conditions identified by the authorized
installer requiring an external RCD.