Troubleshooting
Figure 91: More information about the fault
On the WHMI, internal fault information is shown under Self-Supervision Status.
Figure 92: Internal fault information on Web HMI
Table 9: Internal fault indications and codes
Fault
Fault indication
code
Internal Fault
2
System error
Internal Fault
2
System error
Table continues on the next page
92
Fast self-
Additional
recovery
information
attempt
Start up error:
No
HW/SW mismatch
Start up or runtime
Yes
error: Data bus er-
ror, CPU module
Slow 10min
self-
recovery
Immediate
(# of
attempts)
IRF-mode
No
Yes
Yes (3)
No
1MRS759118 D
Action in permanent fault
state
If relay SW has just been
updated, redo it. If not re-
covered, contact your near-
est ABB representative to
check the next possible
corrective action.
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
REX640
Operation Manual