1MRS759118 D
Table 15: Secondary IP address parameters
Parameter
Configuration/Communica-
tion/Ethernet/Network 2 ad-
dress/ Enable
Configuration/Communica-
tion/Ethernet/Network 2 ad-
dress/IP address
Configuration/Communica-
tion/Ethernet/Network 2 ad-
dress/IP address
Configuration/Communica-
tion/Ethernet/Network 2 ad-
dress/MAC address
The IP address for Network 2 is disabled by default settings, and all Ethernet
ports are assigned to the same IP address used in the Network 1 address menu
Configuration > Communication > Ethernet > Network 1. If Network 2 is taken
into use by the setting Enable="True" (requires reboot), the interlink port X3 of the
COM module is assigned to this second network, using the IP address and subnet
parameters in the Network 2 address menu Configuration > Communication >
Ethernet > Network 2 address.
REX640
Operation Manual
Options
False (default)
TRUE
0.0.0.0
0.0.0.0
xx-xx-xx-xx-xx-xx
If the Network 2 interface is enabled, PTP time synchronization and SMV/
GOOSE multicast are disabled for that port.
Commissioning
Description
Network 2 disabled
Network 2 enabled
IP address for Network 2
Subnet address for Network 2
MAC address for Network 2
117