Rebooting The Software; Restoring Factory Settings; Restoring Relay Backup From Local Hmi - ABB RELION REX640 Operation Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Troubleshooting
6.3.2

Rebooting the software

1.
2.
6.3.3

Restoring factory settings

In case of configuration data loss or any other file system error that prevents the
protection relay from working properly, the whole file system can be restored to
the original factory state. All default settings and configuration files stored in the
factory are restored. Only the ADMINISTRATOR can restore the factory settings.
• Select Configuration > General > Factory setting to restore factory settings.
• Tap Edit, select Activate and tap
The protection relay restores the factory settings and restarts.
6.3.4

Restoring relay backup from local HMI

1.
104
When the relay is in IRF error (the Home button flashes red fast), the
backup is not made.
The relay's device certificate and the CA root certificate are not part of
the backup. If PKI has been configured, this must be reconfigured using
the corresponding tools. In addition, when PKI is in use, CAM settings are
not restored to avoid the condition where the relay is not able to contact
the configured CAM server.
Select Configuration > General > Software reset.
Tap Edit, select Activate and tap
Avoid unnecessary restoring of factory settings, because all the
parameter settings written to the relay will be overwritten with the
default values. During normal use, a sudden change of the settings can
cause a protection function to trip.
Connect the LHMI to the relay
.
.
1MRS759118 D
REX640
Operation Manual