Commissioning
2.
7.5.2.5
Using Protection Monitoring
Protection Monitoring view can be utilized during secondary injection testing.
Instantaneous monitored values are shown on protection characteristics graph.
Refresh rate of monitored value is 500 ms.
1.
2.
3.
148
On the SMV Sending page, check the status of the relay's configured SMV
control blocks and the values of the sent IEC 61850-9-2 sampled value data.
The left side of this page shows a list of the devices where the relay sends
SMV messages. In the system there may be more devices, but these devices are
according to relay configuration the ones subscribing the data from the relay.
The right side of the page shows the SMV data the relay sends to the network.
The sent data has status indicators where green means all OK, yellow warning
and red error.
Figure 129: SMV Sending page
Navigate to Testing and Commissioning page.
Select Protection Monitoring.
Select protection function
1MRS759118 D
REX640
Operation Manual