Thank you for selecting this Emergency Lighting Inverter System (ELI). It provides you with perfect protection for connected loads and equipment. This manual contains Important instructions that should be followed during maintenance of the DSPM Uninterruptible Power Supply. It includes im- portant safety and maintenance instructions for operating the Emergency Lighting Inverter System.
Page 7
DSPM Inc. 439 S Stoddard Ave, San Bernardino, CA 92410 Work Hours: 8 a.m. – 5 p.m. Pacific Standard Time Phone:1(877) DSPM POWER 1(877) 377-6769 After Hours: 5 p.m. – 1 a.m. Pacific Standard Time 1(951) 840-0811 Fax: 1(909) 930-3335 Email: techsupport@dspmanufacturing.com...
A Note notice icon indicates when the user should make a reference of information re- NOTE: garding the UPS operation, load status and display status. Such information is essential if DSPM, Inc. field service assistance and correspondence is required. CAUTION! ENSURE THAT NO FLUIDS OR OTHER FOREIGN OBJECTS CAN ENTER THE INVERTER SYSTEM.
Page 9
THAT POWER IS OFF USING AC AND DC VOLTMETERS BEFORE MAKING CONTACT. DANGER! SOME COMPONENTS WITHIN THE CABINETS ARE NOT CONNECTED TO CHASSIS GROUND. ANY CONTACT BE- TWEEN FLOATING CIRCUITS AND THE CHASSIS IS A LETHAL SHOCK HAZARD. Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual...
Page 10
RELEASED ELECTROLYTE IS HARMFUL TO THE SKIN AND EYES AND MAY BE TOXIC. A BATTERY CAN HAVE A HIGH SHORT CIRCUIT CURRENT AND PRESENT A RISK OF ELECTRICAL SHOCK. THE FOLLOWING PRECAUTIONS SHOULD BE OBSERVED WHEN WORKING ON BATTERIES: Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual...
Page 11
FROM THE MAIN SUPPLY BEFORE INSTALLING AN INTERFACE SIGNAL CABLE. RECONNECT THE POWER ONLY AFTER SIGNALING INTERCONNECTIONS HAVE BEEN MADE DO NOT DISMANTLE THE EMERGENCY LIGHTING IN- VERTER SYSTEM. Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual...
1. INTRODUCTION 1.1. GENERAL The principles of operation described herein are applicable to all models. The DSPM, Inc. Micro Elite Emergency Lighting Inverters are manufactured to provide critical power for lighting during a power outage. The Micro Elite meets or exceeds the life safety codes of UL924 and UL1778.
The on-line DC/AC inverter converts the DC voltage to a pulse-width-modulation (PWM) waveform. This waveform is filtered and reconstructed to a desired AC output and the load is transferred to the inverter. Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual...
The capacity of the Micro Elite may need to be greater than what would be estimated based on the system label require- ments of loads previously discussed. Contact the factory directly if you have any ques-tions about powering unusual loads from your Micro Elite. Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual...
2.4.3. DSP/PWM Smart Battery Monitoring System is TEMPERATURE COMPENSATED maintaining maximum runtime and battery life 2.4.4. Microprocessor controlled recharge and DSP/PWM overcharge protection standard Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual Rev: NR Title: Micro Fax: 909.930.3335...
Modular design and small footprint allow easy installation in electrical closet or other convenient locations 2.10.2. Phone assisted factory start-up standard for all systems 2.10.3. Extended warranty available Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual Rev: NR...
2.11. SPECIAL APPLICATIONS 2.11.1. DSPM offers numerous UL924 optional devices to meet unusual or difficult application parameters normal sw- itching and/or dimming devices in NON-emergency conditions. 2.11.2. ECM - Environmental Circuit Module allows fixtures and lamps on the emergency circuit (s) to be operated by normal switching and/or dimming devices in NON-emergency conditions.
ING TOOLS. EVEN WHEN THE POWER IS OFF, DANGEROUSLY HIGH POTENTIAL VOLTAGES MAY EXIST AT CAPACITOR BANKS. ALWAYS OBSERVE BATTERY PRECAUTIONS WHEN OPERATING NEAR ANY BATTERIES. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT IN DEATH, INJURY OR DAMAGE TO EQUIPMENT. Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual...
4.3. STEPS TO TAKE If any of the above occur: 1) Record information off the System Label. 2) Call DSPM’s Customer Service DANGER! LETHAL VOLTAGES ARE PRESENT INSIDE THE EQUIPMENT EVEN WHEN THERE APPEARS TO BE NO INPUT POWER TO THE UNIT. PROTECT YOURSELF FROM THE RISK ELECTROCUITION BY REFERRING SERVICE TO QUALIFIED PERSONNEL ONLY.
Agreement, the batteries should be tested and measurement taken log in a Batteries Maintenance Log. Failure to maintain a valid batteries log could result in the voiding of all warranties. DSPM recommends the uses and downloading (from: www.DSPManufacturing.com or www.DSPMInc.net) of the Batteries Log. If you chose to use another log, the entries should contain the entries in our recommended log (Please refer to the Batteries Mainte- nance Log in this manual when maintaining your Batteries Log.).
Page 21
Inside the battery cabinet temperature measured by technician when the cabinet is first opened after load test. 4.4.4.H. Ambient Temperature Outside the battery cabinet temperature measured by technician when the cabinet is first opened after load test. negative Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual Rev: NR...
Page 22
Technician The testing Technician should sign in this cell. 4.4.4.V. Date The testing Technician should Date the signing of his/her signature in this cell. Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual Rev: NR Title: Micro Fax: 909.930.3335...
Page 25
3.The Processor will continue starting the system and the Inverter LED lights. Note: The Unit is now on the Inverter. Record the set values for the system below. Log 2 Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual...
Page 26
Note: all recorded voltages should be measure with True RMS meters. Secure cabinet doors; your system is back on line. Report any abnormalities observed in test in the “Results” section below. Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual...
Page 27
CIRCUIT BREAKER INDICATES A SERIOUS PROBLEM THAT MAY RESULT IN SERIOUS INJURY OR DAMAGE TO THE EQUIPMENT IF CIRCUIT BREAKER IS CLOSED WITHOUT KNOWING WHY IT FAILED. CHECK FOR SHORTS IN BATTERY OR CALL DSPM CUSTOMER SERVICE AND SUPPORT FOR ASSISTANCE. WARNING! THE BATTERY ELECTROLYTE IS A DILUTED SULFURIC ACID THAT IS HARMFUL TO THE SKIN AND EYES.
Page 28
Disconnect charging source prior to connecting or disconnecting battery terminals. For the best results, charge the battery for 24 hours after they are hooked up and the ELI is brought on line. Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769...
Page 29
The recipient agrees by accepting this document, not to supply or disclose and information regarding it to any unauthorized person, or to incorporate this data into any other design or use thereof. All patent rights are expressly reserved. Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769...
Page 30
Audible Fault Indicator: An alarm buzzer beeps continuously when an Overload is detected. Verify that the load matches the capability specified in the Unit System Label. 5.1.2 5.1.3 5.1.1 5.1.4 Figure 3 Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual Rev: NR Title: Micro Fax: 909.930.3335...
Page 31
6. OPERATION AND PROCEDURE The initial startup must be done in conjunction with DSPM or by a factory authorized technician. PLEASE CALL FOR STARTUP BEFORE APPLYING POWER TO THE UPS! 6.1. START-UP PROCEDURE 6.1.1. After making all power and grounding connections to the Emergency Lighting Inverter System; ver ify that the system is OFF (Non of the LEDs are lit).
Page 32
✽ This coverage can be performed as an On-Site Startup Service for any DSPM product. ✽ All parts and labor to repair if NOT covered under a current Warranty or Service Plan and will be billed from DSPM current rates unless covered by a current warranty or service plan.
Page 33
✽ This plan covers all replacement parts and labor including travel time and expenses for all emergency calls to ser- vice the unit. All service calls will be made Seven (7) days a week exception of the DSPM’s designated holidays.
Page 34
✽ If the Customer requests remedial maintenance or preventive maintenance outside of the contracted coverage, DSPM will provide this service. This service will be charged to the Customer at DSPM’s standard hourly rates in effect at the time of the service, and will be subject to an available field engineer.
Page 35
✽ DSPM will include installation of any changes for safety reasons and at DSPM option, install any factory enhance- ments and upgrades, and reliability changes or improvements during the preventive maintenance service call. Uninterruptible Power Systems (UPS) and Emergency Lighting Inverter’s batteries are NOT warranted under this plan unless specified.
Page 36
Must be purchased during an active original factory warranty, during an active Extended Warranty, during an active Service Contract, or After a CI with DSPM Management approval. Multiple Unit discount for more then one unit at a single location only, and startups are all at the same time.
Page 37
When insulated grip tools are not available, a method for insulating grips on tools that we use at DSPM using Plasti Dip by Performix is illustrated in Figures 4a-f. The illustration is only an example of how to insulate your tools, i.e. you may want to insulate the open end of the wrench.
Page 38
6. Fan 7. Batteries 8. Power ON/OFF Display 9. Main Input Breaker (CB1) 10. Main Output Breaker (CB3) 11. Main Power Board Figure 5 Phone : 1.877.DSPM.POWER 1.877.377.6769 Phone : 1.877.DSPM.POWER-1.877.377.6769 Title: Micro Elite Maintenance’s Manual Rev: NR Title: Micro Fax: 909.930.3335...
Page 39
The start-up date will be determined only from the completed inspection and start-up sheet provided DSPM to User. The product shipment date will be determined only from the DSPM bill of lading. If any part or portion of the DSPM product fails to conform to the Warranty within the Warranty period, DSPM, at its option, will furnish new or factory remanufactured products for repair or replacement of that portion or part and reinstall the replacement product.
Page 40
Drawings, Descriptions: DSPM warrants for the period and on the terms of the Warranty set forth herein that the covered product will conform to the descriptions contained in the certified drawings, if any, applicable thereto, to DSPM final invoices, and to applicable DSPM product brochures and manuals published as of the date of product shipment (“Descriptions”).
Page 41
Acts of God, theft or installation contrary to DSPM’S recommen- dations or specifications, or in any event if the DSPM (for cabinets) or other manufacturer’s (for batteries) serial number has been altered, defaced, or removed.
Page 42
NO SALESPERSON, EMPLOYEE OR AGENT OF DSPM IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. Warranty terms may be modified, if at all, only in writing and signed by a DSPM official. DSPM obligations under this warranty are conditioned upon timely receipt of full payment of the product purchase price and any amounts due from User under this Warranty.