Hamworthy STRATTON MK3 Series Installation, Commissioning And Servicing Instructions page 89

Table of Contents

Advertisement

For a request via LPB
• LPB network menu
Check that the secondary regulatory is defined on an LPB segment other than 0 (reserved for
the generators)
Set the addresses and segments in your PLC that are shown in the following parameters
For your PLC to be the timestamp master
If you want an alarm report on this module (output K10 (QX1)) containing all the faults from all the
modules
For a request via Modbus
• Setup menu
Configure input H1 :
• Modbus menu
In the boiler's Modbus elements, set the
The Modbus register for sending the boiler flow temperature setpoint
06.02.2023
Diagram: MK3-10
Alarm relay system messages (6611)
STRATTON MK3 - Installation, Use and Maintenance
Line No.
Appliance address (6600)
Segment address (6601)
Bus supply function (6604)
Clock operation (5955)
Function input H1 (5950) Consumer circuit request 1
Contact action direction (5951) Work
Slave address (6651) As it is set on your PLC
Baud rate (6652) As it is set on your PLC
Parity (6653) As it is set on your PLC
Stop bit (6654) As it is set on your PLC
page 6 / 7
Value
1
0
Automatic
Master or Slave with
adjustment if the PLC is
the master clock
Yes
89 / 154