Hamworthy STRATTON MK3 Series Installation, Commissioning And Servicing Instructions page 123

Table of Contents

Advertisement

Line
Programming
no.
2503
Switching wait time
2550
Gas energy meter
2551
Gas meter correction
2560
Exhaust flap stop timer
2630
Auto drain function
2655
Drain function activation time
2656
Drain cut-off duration
2657
Number of repetitions
2662
Hot circuit drain duration
2663
DHW drain duration
Cascade
3510
Cascade operating strategy
3511
Power band, lower limit (PMin)
3512
Power band, upper limit (Pmax)
3530
Integral release sequence generators
3531
Integral reset sequence generators
3532
Restart lock
3533
Sequential generator connection timer
3534
Duration of basic forced speed when generator is
switched on
3535
DHW activation timer
3540
Delay before auto generator cascade switching
3541
Exclusion of auto cascade generator switching
3544
Pilot generator
3560
Minimum cascade return setpoint
3562
Cascade return limit, influence on consumer circuit
Solar
3810
Temperature difference Solar on
3811
Temperature difference Solar off
3812
DHW tank minimum charging temperature
3813
Tank activation differential
3814
Tank stop differential.
3815
Min. storage tank loading temperature
3818
Minimum pool loading temperature
3822
Tank loading priority
3825
Relative priority loading time
3826
Relative priority waiting time
3827
Parallel operation waiting time
3828
Secondary pump start-up timer
3830
Collector start function
3831
Collector pump minimum operating time
3840
Solar collector anti-freeze temperature
3850
Temp. protection against collector overheating
3860
Coolant evaporation temperature
06.02.2023
STRATTON MK3 - Installation, Use and Maintenance
Access
Default value
S
6 s
S
on
S
1
S
30 s
S
Stop
S
10 s
S
5 s
S
3
S
10 min
S
5 min
S
Switch-on early, stop delayed
S
30%
S
90%
S
200 °Cmin
S
100 °Cmin
S
300 s
S
5 min
S
60 s
S
5 min
S
500 h
S
none
S
generator 1
S
8 °C
S
on
S
8 °C
S
4 °C
S
30 °C
S
8 °C
S
4 °C
S
30 °C
S
30 °C
S
DHW tank
S
20 min
S
5 min
S
20 min
S
60 s
S
30 min
S
20 s
S
0 °C
S
120 °C
S
140 °C
Customer setting