LILLIPUT HE GAS/OIL FIRED CAST IRON SECTIONAL BOILERS INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS IMPORTANT NOTE THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING, OPERATING OR SERVICING EQUIPMENT...
Page 3
ON NATURAL GAS (2ND FAMILY) I ONLY. THE LILLIPUT BOILER RANGE HAS BEEN TESTED TO COMPLY WITH THE REQUIREMENTS OF THE GAS APPLIANCE DIRECTIVE (90/396/EEC) EC IDENTIFICATION No. 63AR4194 PUBLICATION NO. 500001047 ISSUE 'F’ SEPTEMBER 2007 HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
Portland pressurisation units are available from (temperature gauge) Hamworthy Heating Ltd for sealed systems. A high low thermostat (not used with current burner options). Construction The boiler is housed in a sheet steel casing which is Lilliput HE sectional boilers are supplied with fully supplied flat-packed for on-site assembly.
GAS CONNECTION(typical) Nominal Bore ¾" ¾" ELECTRICAL SUPPLY 240V ~ single phase fused and rated at 10 A NOTE! Gas input rate based on NGA (G20) gas with a Nett CV of 34.06 MJ/m HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
2.2 Dimensions and Clearances - Fig. 1 Overall Dimensions and Clearances BOILER MODEL Amm Gas* Amm Oil* Dmm.min. LILLIPUT HE 65 LILLIPUT HE 90 *Typical Dimensions based on Riello Burners. HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
Part 1: Fundamentals & design considerations. Part Selection of equipment. Part The Gas Safety (Installation and Use) Regulations Installation, commissioning and maintenance. require that only competent persons, i.e. CORGI British Gas Publications Registered installers, should install HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
2.5 metres of the flue. Oil Supply Lines - The oil supply line(s) between storage tank and burner should be run in copper, The flue should not terminate adjacent to any HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
The boiler room must have, or be provided with, (Combustion (Ventilation) permanent air vents directly to the outside air, at Ventilation) high level and at low level. For an exposed boiler house, air vents should be fitted preferably on all Volume HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
To allow electrical isolation of the boiler when necessary the electrical supply should come from a Minimum System Water Pressure double pole fused isolator (located in the boiler HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
Page 14
TEMPERATURE CONTROL HIGH—LOW LIMIT THERMOSTAT THERMOSTAT THERMOSTAT POWER ON LIGHT PUMP ON / OFF SWITCH SWITCH 14 15 16 17 18 19 6A FUSE 240Vac ~ 50Hz Fig. 2. Boiler Control Panel Wiring Diagram HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
Boiler assembly tools are available on loan, Taking two new nipples, smear them with from Hamworthy Heating Ltd. suitable nipple sealant and insert them into their seatings - ensuring that they are at right angles to the face of the section.
(A) and side edges of the are positioned around rear jacket to the wrap the rear spacers and using duct tape secure in position with duct tape. Fig. 3. Bolier Casing Assembly HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
Page 17
Hook the front cover over the locating heads in the side pan- HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
Check that gas meter is operational and has readings obtained should be as follows:- been checked by the local region of British Gas. 11-12% Check that gas meter and supply pipework is less than 100 ppm HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
Cycle boiler on and off several times to Adjust gas supply governor to achieve at least ensure reliable burner ignition and boiler 17.5 mbar (7.0 in wg) at inlet to boiler gas operation. Check for gas and water leaks. HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
Section 7. Refit burner. Reconnect fuel and SWITCH OFF ELECTRICAL SUPPLY TO BOILER electrical supplies. AT ISOLATOR AND SHUT OFF FUEL SUPPLY Turn fuel supply check TO BOILER. soundness of fuel supply pipework. HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...
Page 21
Check all flue joints for integrity. Check ventilation ducts/grilles to boiler room and ensure they are clear. Re-commission boiler as detailed in relevant parts of Section 8 - Commissioning. HAMWORTHY HEATING LTD LILLIPUT HE 500001047/F...