Hamworthy STRATTON MK3 Series Installation, Commissioning And Servicing Instructions

Hamworthy STRATTON MK3 Series Installation, Commissioning And Servicing Instructions

Table of Contents

Advertisement

STRATTON MK3 SERIES BOILERS
Wall Hung, Condensing, Room Sealed,
Fully Modulating, Pre-Mix,
Gas Fired Boilers for Heating & Domestic
Hot Water Installations
INSTALLATION, COMMISSIONING AND
SERVICING INSTRUCTIONS
Models: S3-40, S3-60, S3-70, S3-80, S3-100, S3-120, S3-150
NATURAL GAS & PROPANE
IMPORTANT NOTE
THESE INSTRUCTIONS MUST BE READ
AND UNDERSTOOD BEFORE INSTALLING,
COMMISSIONING, OPERATING OR
SERVICING EQUIPMENT AND TO BE LEFT
ADJACENT TO THE GAS METER

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the STRATTON MK3 Series and is the answer not in the manual?

Questions and answers

Jim Bisset
May 6, 2025

"According to your Stratton MK3 Series Boiler installation manual, terminals 11 and 12 are typically designated for external control connections. Could you confirm whether these terminals require programming to perform a specific function? Some boilers need configuration within the control settings to recognize external switching inputs—does this apply to the Stratton MK3 Series Boiler? If so, what steps are necessary to carry out this setup?"

User image 6819dde0c91ee

Summary of Contents for Hamworthy STRATTON MK3 Series

  • Page 1 STRATTON MK3 SERIES BOILERS Wall Hung, Condensing, Room Sealed, Fully Modulating, Pre-Mix, Gas Fired Boilers for Heating & Domestic Hot Water Installations INSTALLATION, COMMISSIONING AND SERVICING INSTRUCTIONS Models: S3-40, S3-60, S3-70, S3-80, S3-100, S3-120, S3-150 NATURAL GAS & PROPANE IMPORTANT NOTE...
  • Page 3: Table Of Contents

    STRATTON MK3 - Installation, Use and Maintenance CONTENTS 1. WARNINGS AND RECOMMENDATIONS ................5 1.1. Transport and storage ........................... 5 1.2. Symbols used in this document ........................5 1.3. Qualification of personnel for installation, adjustment, use and maintenance ..........5 1.4. Safety instructions ............................6 1.5. Water characteristics ............................. 8 1.6. Air quality ..............................10 2.
  • Page 4 STRATTON MK3 - Installation, Use and Maintenance 9. HYDRAULIC DIAGRAMS AND CONFIGURATIONS ............52 9.1. Symbols used in the diagrams ........................52 9.2. List of diagrams ............................52 10. SPARE PARTS LIST ......................106 11. CUSTOMER REGULATION PARAMETERS TABLE .............116 12. OPTION KITS ........................132 12.1.Boiler mounted kits ........................... 133 12.2.External kits ..............................
  • Page 5: Warnings And Recommendations

    STRATTON MK3 - Installation, Use and Maintenance 1. WARNINGS AND RECOMMENDATIONS PLEASE READ THIS MANUAL CAREFULLY BEFORE INSTALLING, MAINTAINING AND USING THE BOILER. IT CONTAINS IMPORTANT SAFETY INFORMATION. 1.1. Transport and storage The boiler: - must be stored vertically on a flat surface or in a place where the temperature is between -20°C and +55°C with a relative humidity between 5% and 95%.
  • Page 6: Safety Instructions

    STRATTON MK3 - Installation, Use and Maintenance 1.4. Safety instructions Current Gas Safety (Installation and Use) Regulations or rules in force. The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force. In GB, the installation must be carried out by a suitably qualified Gas Safe registered engineer or in IE by a competent person. It must be carried out in accordance with the relevant requirements of the: • Gas Safety (Installation and Use) Regulations • The appropriate Building Regulations either The Building Regulations, The...
  • Page 7 STRATTON MK3 - Installation, Use and Maintenance BSEN.12831:2017 Heating Systems in buildings: Method for calculation of the design heat load. BSEN.13831 Specification for: Expansion vessels using an internal diaphragm, for sealed hot water heating systems. BSEN.14336:2004 Heating Systems buildings: Installation commissioning of water based heating systems. IGEM/UP/1 Soundness testing and purging of industrial and commercial gas installation IGEM/UP/2 Gas installation pipework, boosters and compressors on industrial and commercial premises. IGEM/UP/10 Installation of gas appliances in industrial and commercial premises.
  • Page 8: Water Characteristics

    IMPORTANT. use of non-recommended inhibitors may impact boiler warranty Hamworthy recommend Water Treatment in accordance with the Benchmark Guidance Notes on Water Treatment in Central Heating Systems. If water treatment is used Hamworthy recommend only the use of SCALEMASTER SM-1 PRO, FERNOX, MBI, ADEY MC1 or SENTINEL X100 inhibitors and associated water treatment products, which must be used in accordance with the manufacturers’ instructions.
  • Page 9 STRATTON MK3 - Installation, Use and Maintenance 3. In hard water areas, treatment to prevent limescale may be necessary - the use of artificially softened water is permitted when filling the system, where the cold supply is fitted with a water softening device. 4. Under no circumstances should the boiler be fired before the system has been thoroughly flushed. 1.5.3. Protecting steel and stainless steel boilers against corrosion Corrosion can affect the iron components used in boilers and heating systems, which is directly related to the presence of oxygen in the water heater's water. Dissolved oxygen that enters the unit when it is being filled...
  • Page 10: Air Quality

    STRATTON MK3 - Installation, Use and Maintenance If any of these parameters deviates from the above recommendations, refer to a water treatment specialist to correct the problem. 1.5.5. Installation of the plate heat exchanger If the recommendations listed above cannot be met, you can set up a plate exchanger to separate the primary system from the secondary system, which protects the boiler from undesirable effects. 1.5.6. Setting up a filtration system A filtration system on the back of the boiler is recommended in order to remove suspended particles from the unit (filter, sediment trap, etc.) .
  • Page 11: Approvals

    STRATTON MK3 - Installation, Use and Maintenance 2. APPROVALS 2.1. Compliance with UK Directives - Satisfies the essential requirements of the Electrical Equipment (Safety) Regulations 2016 and is manufactured in accordance with the UK designated standards. - Satisfies the essential requirement of the Electromagnetic Compatibility Regulations 2016 and is manufactured in accordance with the UK designated standards.
  • Page 12: Gas Supply Pressures

    STRATTON MK3 - Installation, Use and Maintenance 2.4. Gas supply pressures The pressures provided below must be taken at the input to the gas INFORMATION: valve. Natural gas H Propane gas Nominal pressure (mbar) Minimum pressure (mbar) Maximum pressure (mbar) 00U07428680-C 12 / 154...
  • Page 13 STRATTON MK3 - Installation, Use and Maintenance 06.02.2023 13 / 154...
  • Page 14: Technical Specifications

    STRATTON MK3 - Installation, Use and Maintenance 3. TECHNICAL SPECIFICATIONS 3.1. Dimensions Figure 1 - Dimensional characteristics 00U07428680-C 14 / 154...
  • Page 15 STRATTON MK3 - Installation, Use and Maintenance MODELS in kW (mm) Boiler width (mm) Boiler depth (mm) Boiler height (mm) Fixing centers (mm) Distance of fixings to side of boiler (mm) Fixing point centers above top of casing (mm) 108.5 Center of connections to rear of boiler 66.5 65.5 Center of siphon outlet to side casing (mm) 73.5 74.5 Center of return connection from casing side Centers between flow and return (mm) connections Centers between gas inlet and return...
  • Page 16: Boiler Components

    STRATTON MK3 - Installation, Use and Maintenance 3.2. Boiler components Air pressure switch Température sensor Ignition transformer Ionization and ignition electrode Gas valve Condensate siphon (supplied unmounted) Water return temperature sensor Bleed valve 10 Water outlet temperature sensor 11 Water pressure sensor 12 Water flow meter 13 EMC filter (on 55 kW) 00U07452020-A Figure 2 - Boiler components for 40 to 70 models...
  • Page 17 STRATTON MK3 - Installation, Use and Maintenance Air pressure switch Temperature sensor Ignition transformer Ignition electrode gas valve Condensate siphon (supplied unmounted) EMC filter Water return temperature sensor 10 Trap 11 Water outlet temperature sensor 12 Ionization electrode 13 Pressure sensor 14 Flowmeter 00U07425540-A Figure 3 - Boiler components for 80 to 120 models Note: in order to facilitate viewing, the side covers have been removed, but these cannot be removed 06.02.2023...
  • Page 18 STRATTON MK3 - Installation, Use and Maintenance Air pressure switch Flue gas temperature probe Ignition transformer Ignition electrode Gas valve Condensate siphon (supplied unmounted) EMC filter Water return temperature sensor Bleed valve Water outlet temperature sensor Ionization electrode Water pressure sensor Water flow meter Figure 4 - Boiler components for 150 model Note: in order to facilitate viewing, the side covers have been removed, but these cannot be removed 00U07428680-C 18 / 154...
  • Page 19: Combustion At 15°C And 1013 Mbar

    STRATTON MK3 - Installation, Use and Maintenance 3.3. Combustion at 15°C and 1013 mbar 3.3.1. G20 natural gas MODELS in kW Nominal power Pn (80/60°C) 38.8 53.4 67.8 77.8 93.4 116.8 141.1 Nominal power when condensing P 42.2 58.0 73.6 84.4 101.3 127.8...
  • Page 20 STRATTON MK3 - Installation, Use and Maintenance 3.3.2. G31 Propane Gas (for relevant models and destination countries) MODELS in kW Nominal power Pn (80/60°C) 38.8 53.4 67.8 77.8 93.4 116.8 Nominal power when condensing P 42.3 58.1 73.7 84.5 101.4 127.9 (50/30°C) Minimum power Pmin...
  • Page 21: Operating Conditions

    Electrical power consumed at Pn (excluding accessories) Electrical power consumed at 30% of Pn (excluding accessories) Electrical power consumed at Pn with Hamworthy-supplied boiler circulator 100.0 171.0 220.0 178.0 251.0 365.0 550.0 (excluding accessories) Electrical power consumption in standby mode DHW sensor: 10 Outdoor sensor: 40 in 0.5 mm² (120 in 1.5 mm²)
  • Page 22: Installation

    STRATTON MK3 - Installation, Use and Maintenance 4. INSTALLATION The boiler is delivered with: - A plan for helping fix the boiler to the wall. - Two mounting hooks. - A 4 bar (models below 70 kW) or 6 bar (models above 80 kW) safety valve. - A plastic funnel that is adapted to the safety valve. - A siphon and a flexible hose for evacuating condensates. - An information plate for the 40 to 120 kW models switching to propane gas. - A gas adapter for the 70 to 120 kW models switching to propane gas. The boiler must not bear the weight of the accessories and connections IMPORTANT: (hydraulics, gas, exhaust system, etc.). 4.1. Installing the boiler The use of the fixing hooks supplied with the product or our supports WARNING : is mandatory.
  • Page 23 STRATTON MK3 - Installation, Use and Maintenance STRATTON MK3 boilers must not be mounted on a wall covered with an inflammable material: plastic, wood, etc. The combustion air must be free of agents containing chlorine, ammonia, fluorine and alkaline. These compounds are found in aerosols, paints, cleaning products, washing powder, detergents, glue, snow- clearing salt, etc. Do not draw in the air that is evacuated from places where these products are used - swimming pools, laundries, hair dressing salons, cold rooms - as one or more of these compounds could be introduced into the combustion air.
  • Page 24: Removing / Installing The Front Panel

    STRATTON MK3 - Installation, Use and Maintenance 4.2. Removing / installing the front panel  Pull the bottom of the panel forwards to release.  Lift the front panel to remove it and free the 2 lugs.  Perform the operation in reverse to reassemble.  Figure 7 - Removing the front cover 4.3. Flue connection Covered by Gas Safe reference.
  • Page 25 STRATTON MK3 - Installation, Use and Maintenance 4.3.1. Ventilation BOILERS NOT EXCEEDING 70kW The ventilation requirements of these boilers is dependent on the type of flue system used, and their heat input. All vents must be permanent with no means of closing and positioned to avoid accidental obstruction by blocking or flooding. Detail reference should be made to BS. 5440 Pt. 2. In IE refer to the current edition of I.S. 813. The following notes are for general guidance only: If installed as a room sealed appliance in a room or internal space, then no purpose provided ventilation is required. If installed as an open flued appliance in a room or internal space, then a permanent air vent is required. The sizes given below are for vents directly communicating with outside air. For other situations refer to BS. 5440 Pt. 2. In IE refer to the current edition of I.S. 813 Ventilation Requirements (not exceeding 70kW net Input) when installed in a compartment. If installed in a compartment, then permanent air vents are required at high and low level.
  • Page 26 STRATTON MK3 - Installation, Use and Maintenance 4.3.2. Connection to a B23 chimney B23 type connection: Air from the installation premises, gas evacuation through the roof via a natural draft pipe. Check that the boiler installation premises have high and low IMPORTANT: ventilation, that it conforms to current regulations and that it is not obstructed.
  • Page 27 STRATTON MK3 - Installation, Use and Maintenance The A dimension indicates the height of the chimney adapter when fully inserted relative to the upper panel of the boiler. Figure 8 - Dimensioning recommendations 4.3.3. Connection to a B23P chimney B23P type connection: Air from the installation premises, gas evacuation through the roof via a pressurised duct.
  • Page 28 STRATTON MK3 - Installation, Use and Maintenance The combustion product extraction duct must be dimensioned by using the parameters set out in the table in chapter 3.3. Depending on the actual configuration of the duct, a calculation is IMPORTANT: required to check that the pressures at the boiler outlet at Qmin, Qall and Qn do not exceed the maximum allowable values in this table.
  • Page 29 STRATTON MK3 - Installation, Use and Maintenance 4.3.4. Assembling the flue Flue terminals or extension ducts may be cut to shorter lengths if required When cutting a duct ensure it is square by marking the length all the way around and only cut back the plain end. When cutting concentric duct, it is important that the inner duct is maintained at 20mm longer than the outer duct to allow correct connection of the ducts. Care should be taken to support the inner duct when cutting the flue. When assembling only use water as a lubricant. Note. Horizontal flue runs must be angled down between1.5° - 3° towards the water heater to allow the condensate to drain. For this reason, it is recommended that a support bracket is used for every 1m of extension pipe. See below for flue assembly examples.
  • Page 30 STRATTON MK3 - Installation, Use and Maintenance 4.3.5. FLUE TERMINATION POSITION IMPORTANT INFORMATION Install the flue in accordance to BS 5440:1 2008 Position the terminal, so the products of combustion do not cause a nuisance. The flue is secured in the wall using either sand and cement or heatproof silicone. The flue must be supported by a bracket every meter of flue length and at every change of direction. Due to the high efficiency pluming will occur. For this reason, vertical termination is recommended, and in any case, terminal positions which could cause problems should wherever possible be avoided.
  • Page 31 STRATTON MK3 - Installation, Use and Maintenance 4.3.5.1. Horizontal flue positions Refer to table 1 4.3.5.2. VERTICAL FLUE POSITIONS Refer to table 1 HEAT INPUTS IN EXCESS OF 70kW NETT For boiler installations with total heat inputs in excess of 70kW nett, reference should be made to BS6644 and IGEM/UP/10.
  • Page 32 STRATTON MK3 - Installation, Use and Maintenance 4.3.6. Connection to a C13 or C33 suction pipe C13 type connection: Air inlet and gas evacuation through concentric ducts connected to a horizontal concentric terminal (suction pipe). C33 type connection: Air inlet and gas evacuation through concentric ducts connected to a vertical concentric terminal.
  • Page 33 STRATTON MK3 - Installation, Use and Maintenance The ignition speed MUST be modified on the 150 kW boilers. Place the boiler in standby mode (see § 3.3.1 of the NAVISTEM B3100 boiler command table instructions). If necessary, press the ESC button to return to the main screen. Open the Safety unit menu. WARNING: Adjust the ignition speed parameter (9512): Connection type 9512 (rpm) B23 / B23P...
  • Page 34: Gas Connection

    STRATTON MK3 - Installation, Use and Maintenance 4.3.7. Condensate removal Removal to the drains, via a drain hopper, using a P.V.C tube (minimum diameter 32 mm) is mandatory because the condensates are acid and thus aggressive (pH between 3 and 5). Use a sufficient slope of the order of 3% to ensure correct flow of the condensates.
  • Page 35: Changing Gas (G20 To G31 For Only 40 To 120 Kw Boilers)

    STRATTON MK3 - Installation, Use and Maintenance 4.5. Changing gas (G20 to G31 for only 40 to 120 kW boilers) This STRATTON MK3 boiler has been adjusted in the factory to work with group H (type G20) natural gas with a supply pressure of 20 mbar. Any operations involving changing the type of gas used must be IMPORTANT: performed by a qualified professional. The valve must be adjusted on the boiler operating at the maximum power and the minimum power. To change gas type, use the operation mode "Manual power adjustment" (see point 3.3.4 in the instructions for the NAVISTEM B3100 boiler controller) which enables the user to switch straight to the...
  • Page 36 STRATTON MK3 - Installation, Use and Maintenance Crank flange screw (x4) Gas valve Propane Injector STRATTON MK3 ø 70 : STRATTON MK3 ø 80 / 100 : STRATTON MK3 ø 120 : Screw (x4) 00U07446410-A Figure 11 - Installing the propane injector 4.5.2. Changing the ignition, pre-ventilation, minimum and maximum speeds Place the boiler in standby mode (see § 3.3.1 of the NAVISTEM B3100 boiler command table instructions).
  • Page 37 STRATTON MK3 - Installation, Use and Maintenance 4.5.3. Adjusting the gas valve - Before starting the burner, on the gas valve, preset the gas flow rate, using the gas flow rate adjustment screw Throttle/R1, to the appropriate value given in the table below. Throttle/R1 - Start the burner at maximum power.
  • Page 38 STRATTON MK3 - Installation, Use and Maintenance Checking the door closed settings Model Throttle gas flow adjustment screw preset Indicative and Offset regulator setpoint adjustment screw / G20 Pmax Pmin Throttle open 6.75 turns / on closing 8.8 / 9.2 9.6 / 10 2 closing turns on throttle 10.3 / 10.7 10.8 /11.2...
  • Page 39: Hydraulic Connection

    STRATTON MK3 - Installation, Use and Maintenance 4.6. Hydraulic connection The boiler irrigation flow rate must be at least equal to Pinst/25 (Pinst = instantaneous power in Th/h - 1 Th/h = 1.163 kW). The circulation pump must be sized according to the maximum power delivered.
  • Page 40 STRATTON MK3 - Installation, Use and Maintenance Safety valve connection (1/2” female) Condensate evacuation Gas supply Flow Return Figure 16 - Elements Filling the installation: The system must be fully vented to remove all air. This will be more effective if the boiler is filled slowly when cold, while keeping: • the manual drain of the exchanger open, When these two parts discharge a continuous flow of water that is free of air, close them and stop filling. Limit hydraulic noise by carefully purging the installation, limiting INFORMATION: water speeds, and letting the pipes expand freely. If there is a risk of freezing, start up the installation then leave the boiler powered (refer to the Navistem B3100 manual).
  • Page 41: Electrical Connection

    STRATTON MK3 - Installation, Use and Maintenance 4.7. Electrical connection Ensure that the general electrical power supply has been cut off WARNING: before starting any repair work. It is mandatory to connect this boiler correctly to earth and to comply with standard for low-voltage electrical installations.
  • Page 42 STRATTON MK3 - Installation, Use and Maintenance 4.7.2. Cable ways Pass example cable Boiler power supply Cable passages for power Cable passage for signal connections (alarm report, heating connections circuit circulators, DHW circulator, (probes, communication mixing valves, etc.). bus, etc.). 00U07444890-A Figure 18 - Packing glands Copper conductor Cable Terminal strips cross-section Power supply Power supply 3 x 1,5 mm² Power QX1, QX2, QX3 3 x 1 mm²...
  • Page 43 STRATTON MK3 - Installation, Use and Maintenance 4.7.5. Connection of the boiler circulation pump (compulsory accessory) 4.7.5.1. Accessory supplied by Hamworthy If the accessory is supplied by Hamworthy, please refer to appendix list. 4.7.5.2. Accessory supplied by the customer The circulation pump is controlled by a 230 VAC (1A max.) output on the NAVISTEM B3100 panel.
  • Page 44 STRATTON MK3 - Installation, Use and Maintenance Figure 19 - Wiring diagram 44 / 154 00U07428680-C...
  • Page 45 STRATTON MK3 - Installation, Use and Maintenance 06.02.2023 45 / 154...
  • Page 46: First Use

    STRATTON MK3 - Installation, Use and Maintenance 5. FIRST USE 5.1. Checks before first use Check that the cold pressure is a minimum of 1 bar. If this is a boiler house renovation, ensure that flushing and if necessary silt removal from the installation have been correctly done (see paragraph 1.5, page 8 of this manual). Verify the connecting of the gases according to the type of chimney.
  • Page 47: Checks After Commissioning

    STRATTON MK3 - Installation, Use and Maintenance 6. CHECKS AFTER COMMISSIONING 6.1. Condensate removal Check that the removal of condensate is not obstructed, on both the boiler side and the pipe side. 6.2. Gas supply Check that the gas pipe diameter is correctly sized: It is necessary to stop all the boilers together abruptly using the boiler room main circuit breaker to check that the gas pressure regulator safety device is not triggered. If this is triggered, the gas pipe is undersized. After this operation, reengage the circuit breaker. The boilers must start automatically, if not, consult the supplier of the gas pressure regulator.
  • Page 48: Maintenance Operations

    STRATTON MK3 - Installation, Use and Maintenance 7. MAINTENANCE OPERATIONS UK would require Gas Safe installer. In IE by a Registered Gas Installer (RGII). Before performing the following operations: • Switch off the main circuit breaker. • Close the gas supply isolation valve. •...
  • Page 49: Annual Checks

    STRATTON MK3 - Installation, Use and Maintenance 7.2. Annual checks • Switch off the electric power supply of the boiler, • Close the gas supply, • Remove the front panel (see § 4.2). Protect all the electric connectors inside the control panel when WARNING: working on the boiler hydraulics (risk of splashing). • Disconnect the gas pipe after the gas valve j, • Disconnect the electrodes, the fan and the air transfer pipe at the air pressure switch, • Unscrew the 4 M6 door fixing nuts , • Remove the burner holder assembly, fan, venturi,...
  • Page 50 STRATTON MK3 - Installation, Use and Maintenance • The geometry of the electrodes, the absence of alumina deposit, the appearance of the ceramic and the seals must be checked. If the electrodes and gaskets are damaged, replace them. • Clean the siphon and check the correct flow of condensates through it. The siphon must be filled with water after maintenance. • Install the burner door and tighten the M6 nuts in rotation (four nuts on 40 to 70 kW models, six nuts on 80 to 150 kW models). Maximum tightening torque: 5 Nm. • Connect the gas supply. • Check that the gas circuit is sealed with a foaming product.
  • Page 51: End Of Product Life

    STRATTON MK3 - Installation, Use and Maintenance 8. END OF PRODUCT LIFE Regulatory disposal and managed recycling of this product can prevent damage to the environment and health risks. a) For the disposal of the product and the component parts, the services of an accredited waste disposal company should be used. b) For more information on waste disposal/management, contact the Local Authority responsible for waste management or the point of sales where the product was purchased 06.02.2023 51 / 154...
  • Page 52: Hydraulic Diagrams And Configurations

    STRATTON MK3 - Installation, Use and Maintenance 9. HYDRAULIC DIAGRAMS AND CONFIGURATIONS 9.1. Symbols used in the diagrams Symbol Function Symbol Function Isolation valve open Balancing valve Motorised 2-channel valve Motorised 3-channel valve Filtered Anti-return flap Safety unit Pump Sediment trap Bleed valve Outdoor sensor Temperature sensor 9.2.
  • Page 53: Boiler Only

    STRATTON MK3 - Installation, Use and Maintenance Diagram Boiler only MK3-1 Control from and existing BMS page 1 / 5 A. HYDRAULIC DIAGRAM EXISTING BMS OCI 351 or OCI 345 Figure 24 - VFO1 diagram B. OPTIONAL ACCESSORIES Quantity Appliance reference Communication kit for LPB bus OCI 345 Communication kit for Modbus bus...
  • Page 54 2 / 5 C. RECOMMENDED HYDRAULIC ACCESSORIES We offer a wide range of hydraulic accessories, including support foam header kits and the PHEX separation system. Please refer to specific Hamworthy literature for detailed information on these products. D. OPERATING DESCRIPTION The existing regulation system controls the installation’s heating circuit.
  • Page 55 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-1 page 3 / 5 E. CUSTOMER’S ELECTRICAL CONNECTION Variant option 0-10V Control by 0.10V signal Boiler pump control LPB bus control Variant Variant Modbus LPB option option Modbus bus control Secondary bottle sensor (B10) For the installation of a pump from your supply, see page...
  • Page 56 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-1 page 4 / 5 F. SPECIFIC START-UP PROCEDURE " Correctly install and connect the electrical connections. " Make the settings below in "specialist" mode: Short press Press for 3 seconds End user Start-up Specialist Line No. Value • Time and date menu Hour / minute (1) HH.MM Set the time Day / month (2) DD.MM...
  • Page 57 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-1 page 5 / 5 Line No. Value • Option: to keep the generator at a stop, even if the 0...10V signal is different from 0 Configure the input that allows blocking H5 input function (5977) Blocked generator, waiting Input action direction H5 Reverse logic to define the release (5978) For a request via LPB • LPB network menu Set the addresses and segments from the following settings in your PLC Appliance address (6600) 1...
  • Page 58: Control 1 Mixed Circuit And Production Of Dwh

    STRATTON MK3 - Installation, Use and Maintenance Diagram Boiler only MK3-2 Control 1 mixed circuit and production of DWH page 1 / 5 A. HYDRAULIC DIAGRAM DHW LOOP Figure 25 - MK3-2 diagram B. OPTIONAL ACCESSORIES Quantity Appliance reference Outdoor sensor kit QAC 34 DHW sensor kit QAZ 36 Boiler pump supplied by the customer...
  • Page 59 2 / 5 C. RECOMMENDED HYDRAULIC ACCESSORIES We offer a wide range of hydraulic accessories, including support foam header kits and the PHEX separation system. Please refer to specific Hamworthy literature for detailed information on these products. D. OPERATING DESCRIPTION The water law of the heating circuit is programmed on the NAVISTEM B3100 with a weekly heating programme.
  • Page 60 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-2 page 3 / 5 E. CUSTOMER’S ELECTRICAL CONNECTION POWER CONNECTION Module 1 Mixing valve QX21 Heating circuit n°2 BX22 Y5/Y6 QX22 Regulated circuit output Heating circuit No. 2 AGU 2.550 sensor B12 BX21 circulator Q6 QX23...
  • Page 61 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-2 page 4 / 5 SIGNALS CONNECTION F. SPECIFIC START-UP PROCEDURE " Correctly install and connect the electrical connections. " Make the settings below in "specialist" mode: Short press Press for 3 seconds End user Start-up Specialist Line No. Value • Time and date menu Hour / minute (1) HH.MM Set the time...
  • Page 62 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-2 page 5 / 5 Line No. Value • Configuration menu Heating circuit 1 (5710) Start Start up heating circuit 1 Relay output QX1 (5890) Alarm output K10 Configure the alarm output Relay output QX2 (5891) DHW pump Q3 Configure the DHW pump output Configure the secondary flow pump...
  • Page 63: Regulated Circuits, 1 Direct Circuit With Low Limit And Production Of Dwh

    STRATTON MK3 - Installation, Use and Maintenance Boiler only Diagram MK3-3 2 regulated circuits, 1 direct circuit with low limit and production of DWH page 1 / 6 A. HYDRAULIC DIAGRAM DHW LOOP Figure 26 - MK3-3 diagram B. OPTIONAL ACCESSORIES Quantity Appliance reference DHW sensor kit...
  • Page 64 2 / 6 C. RECOMMENDED HYDRAULIC ACCESSORIES We offer a wide range of hydraulic accessories, including support foam header kits and the PHEX separation system. Please refer to specific Hamworthy literature for detailed information on these products. D. OPERATING DESCRIPTION The water law of the heating circuit is programmed on the NAVISTEM B3100 with a weekly heating programme.
  • Page 65 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-3 page 3 / 6 E. CUSTOMER’S ELECTRICAL CONNECTION POWER CONNECTION AGU 2.550 AGU 2.550 40- >120 Module 1 Mixing valve QX21 Heating circuit n°2 BX22 Y5/Y6 QX22 Regulated circuit Heating circuit No. 2 AGU 2.550 output sensor B12 BX21...
  • Page 66 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-3 page 4 / 6 SIGNALS CONNECTION Room thermostat (Opentherm bus) 00U07428680-C 66 / 154...
  • Page 67 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-3 page 5 / 6 F. SPECIFIC START-UP PROCEDURE " Correctly install and connect the electrical connections. " Make the settings below in "specialist" mode: Short press Press for 3 seconds End user Start-up Specialist IMPORTANT: configure the switches on the AGU 2.550 extension modules. Line No.
  • Page 68 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-3 page 6 / 6 Line No. Value • Menu Heating circuit 1/2/3 Comfort setpoint temperature ---°C Adjust the comfort setting (710/1010/1310) Curve slope (720/1020/1320) Adjust the curve slope Minimum flow temperature setpoint 60°C (adjust according Adjust the min. flow temperature for (740) to the lower limit) heating circuit 1...
  • Page 69: Regulated Circuits, And Dhw Production

    OCI 345 C. RECOMMENDED HYDRAULIC ACCESSORIES We offer a wide range of hydraulic accessories, including support foam header kits and the PHEX separation system. Please refer to specific Hamworthy literature for detailed information on these products. 06.02.2023 69 / 154...
  • Page 70 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-4 page 2 / 8 D. OPERATING DESCRIPTION The heating water law is programmed on the NAVISTEM B3100, with or without a low temperature limit and with a weekly programme. The AGU2.550 interfaces are used to control the two three-way regulating valves of the heating networks. The other 2 will be controlled by the RVS63 integrated in an external unit. The boiler operates in variable flow temperature according to the outdoor temperature measured by the exterior sensor QAC 34, without a low temperature limit. The production of domestic hot water is controlled by the NAVISTEM B3100 using the QAZ 35 sensor in the tank. 00U07428680-C 70 / 154...
  • Page 71 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-4 page 3 / 8 E. CUSTOMER’S ELECTRICAL CONNECTION POWER CONNECTION Module 1 Mixing valve QX21 Heating circuit n°2 BX22 Y5/Y6 QX22 Regulated circuit Heating circuit No. 2 AGU 2.550 output sensor B12 BX21 circulator Q6 QX23...
  • Page 72 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-4 page 4 / 8 STRATTON MK3 SIGNALS CONNECTION 00U07428680-C 72 / 154...
  • Page 73 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-4 page 5 / 8 RVS 43 or RVS 63 regulator unit: Regulated circuit Varino bus Regulated circuit output sensor B12 connection output sensor B1 F. SPECIFIC START-UP PROCEDURE " Correctly install and connect the electrical connections. "...
  • Page 74 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-4 page 6 / 8 Line No. Value • Configuration menu Configure the secondary flow sensor BX2 sensor input (5931) B10 line output sensor Heating circuit 1 (5710) Start Start up heating circuit 1 Heating circuit 2 (5715) Start Start up heating circuit 2 Relay output QX1 (5890)
  • Page 75 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-4 page 7 / 8 Line No. Value Refer to the "OPTIMISATION" chapter for configuring the time slots for the heating and DHW circuits as well as for programming the anti-legionella cycles. On the RVS 63: " Correctly install and connect the electrical connections. " Make the settings below in "specialist" mode: Short press End user Start-up Press for 3 seconds Specialist Line No. Value •...
  • Page 76 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-4 page 8 / 8 Switch the heating regime to permanent comfort • Domestic hot water menu Comfort setting (1610) ---°C Adjust the DHW setpoint Activate the DHW mode Refer to the “ELECTRICAL VALIDATION” chapter for the regulator input/output tests Refer to the "OPTIMISATION" chapter for configuring the time slots for the heating and DHW circuits as well as for programming the anti-legionella cycles. 00U07428680-C 76 / 154...
  • Page 77: Non-Regulated Circuit With Sliding Flow

    STRATTON MK3 - Installation, Use and Maintenance Diagrams Boiler only MK3-20, 1 non-regulated circuit with sliding flow page 1 / 4 A. HYDRAULIC DIAGRAM Figure 28 - MK3-20 diagram The boiler operates in variable flow temperature according to the outdoor temperature measured by the exterior sensor QAC 34. The heating water law is programmed on the NAVISTEM B3100, with or without a low temperature limit and with a weekly programme. The heating pump must be able to operate at a constant speed to ensure the minimum flow rate that is required by the generator. If the installation is equipped with thermostatic taps on the emitters, the bypass between the outward and return lines of the network is essential. It is equipped with a differential valve that allows for the free flow of the heating pump when the thermostatic taps close.
  • Page 78 STRATTON MK3 - Installation, Use and Maintenance Diagrams: MK3-20 page 2 / 4 B. NECESSARY REGULATION ACCESSORY Quantity Appliance reference Outdoor sensor kit QAC 34 00U07428680-C 78 / 154...
  • Page 79 STRATTON MK3 - Installation, Use and Maintenance Diagrams: MK3-20 page 3 / 4 C. CUSTOMER’S ELECTRICAL CONNECTION POWER CONNECTION External sensor B9 06.02.2023 79 / 154...
  • Page 80 STRATTON MK3 - Installation, Use and Maintenance Diagrams: MK3-20 page 4 / 4 D. SPECIFIC START-UP PROCEDURE " Correctly install and connect the electrical connections. " Make the settings below in "specialist" mode: Short press Press for 3 seconds End user Start-up Specialist Line No. Value • Time and date menu Hour / minute (1) HH.MM Set the time...
  • Page 81: Cascaded Boilers

    STRATTON MK3 - Installation, Use and Maintenance Cascaded boilers Diagram MK3-24 DHW production with tank with coil page 1 / 3 A. HYDRAULIC DIAGRAM DHW LOOP Figure 29 - MK3-24 diagram B. REQUIRED REGULATION ACCESSORY Quantity Appliance reference DHW sensor kit QAZ 36 C.
  • Page 82 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-24 page 2 / 3 D. CUSTOMER'S ELECTRICAL CONNECTION POWER CONNECTION SIGNALS CONNECTION DHW sensor B3 00U07428680-C 82 / 154...
  • Page 83 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-24 page 3 / 3 E. SPECIFIC START-UP PROCEDURE " Correctly install and connect the electrical connections. " Make the settings below in "specialist" mode: Short press Press for 3 seconds End user Start-up Specialist Line No. Value • Time and date menu Hour / minute (1) HH.MM Set the time...
  • Page 84: Without Control Of The Secondary Communications Networks 0

    QAD 36 C. RECOMMENDED HYDRAULIC ACCESSORIES We offer a wide range of hydraulic accessories, including support foam header kits and the PHEX separation system. Please refer to specific Hamworthy literature for detailed information on these products. 00U07428680-C 84 / 154...
  • Page 85 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-10 page 2 / 7 D. OPERATING DESCRIPTION The existing regulation controls all the circuits of the installation. It determines the outlet set point temperature that the installation requires and sends it to the boilers, either in a 0 - 10V signal directly to the NAVISTEM B3100 that is the master of the cascade, or over the LPB bus or Modbus to each NAVISTEM B3100. The cascade of boilers is controlled by the installation’s regulation system according to the needs. The setpoint sent reflects the heating temperature that the installation needs at this precise moment. E. CUSTOMER'S ELECTRICAL CONNECTION Boiler 1 0-10V Next boiler 06.02.2023 85 / 154...
  • Page 86 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-10 page 3 / 7 Boiler 2 and following Boiler pump supplied with the kit For the installation of a pump from your supply, see page 119 at the end of the document 00U07428680-C 86 / 154...
  • Page 87 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-10 page 4 / 7 Boiler 2 and following 0-10V Next boiler Previous boiler 06.02.2023 87 / 154...
  • Page 88 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-10 page 5 / 7 F. SPECIFIC START-UP PROCEDURE " Correctly install and connect the electrical connections. " Make the settings below in "specialist" mode: Short press End user Start-up Specialist Press for 3 seconds On boiler 1 (cascade master boiler) Line No.
  • Page 89 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-10 page 6 / 7 Line No. Value For a request via LPB • LPB network menu Check that the secondary regulatory is defined on an LPB segment other than 0 (reserved for the generators) Set the addresses and segments in your PLC that are shown in the following parameters Appliance address (6600) Segment address (6601) Bus supply function (6604) Automatic For your PLC to be the timestamp master Clock operation (5955) Master or Slave with adjustment if the PLC is...
  • Page 90 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-10 page 7 / 7 Line No. Value On Boiler 2 and following • LPB network menu Set the addresses and segments from the following settings in your PLC Appliance address (6600) 1 Segment address (6601) 0 Clock operation (5955) Slave without adjustment For your PLC to be the timestamp master •...
  • Page 91: Regulated Circuits Per Boiler And Production Of Dhw

    QAD 36 C. RECOMMENDED HYDRAULIC ACCESSORIES We offer a wide range of hydraulic accessories, including support foam header kits and the PHEX separation system. Please refer to specific Hamworthy literature for detailed information on these products. D. OPERATING DESCRIPTION The master NAVISTEM B3100 controls the cascade of boilers on the basis of the outlet temperature measured by the sensor QAD 36. Each NAVISTEM B3100 controls the charge...
  • Page 92 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-11 page 2 / 7 E. CUSTOMER'S ELECTRICAL CONNECTION Boiler 1 Boiler pump supplied with the kit For the installation of a pump from your supply, see page 119 at the end of the document Module 1 Mixing valve QX21...
  • Page 93 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-11 page 2 / 7 Boiler 2 and following Next boiler Previous boiler 06.02.2023 93 / 154...
  • Page 94 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-11 page 2 / 7 E. SPECIFIC START-UP PROCEDURE " Correctly install and connect the electrical connections. " Make the settings below in "specialist" mode: Short press End user Start-up Specialist Press for 3 seconds On boiler 1 (cascade master boiler) Line No.
  • Page 95 STRATTON MK3 - Installation, Use and Maintenance Diagram: MK3-11 page 2 / 7 Line No. Value • Domestic hot water menu Comfort setting (1610) ---°C Adjust the DHW setpoint Activate the DHW mode On boiler 2 and following (cascade slave boiler) • Configuration menu Start up heating circuit 1 Heating circuit 1 (5710) Start...
  • Page 96 STRATTON MK3 - Installation, Use and Maintenance ELECTRICAL VALIDATION page 1 / 1 ELECTRICAL VALIDATION Line No. Value • Menu Input/output tests Check the sensor values External T° B9 (7730) ---°C Outdoor T° B9 T° ECS B3 (7750) ---°C DHW sensor B3 T° sensor BX2 (7821) ---°C BX2 sensor (cascade or secondary B10 cylinder flow)
  • Page 97 STRATTON MK3 - Installation, Use and Maintenance OPTIMISATION page 1 / 4 HEATING CIRCUIT OPTIMISATION Reduce setpoints for time ranges Line No. Value • Menu Heating circuit (1 or 2 or 3) Reduced setpoint T° (712) ...°C Adjust the reduced setpoint for CH1 Adjust the reduced setpoint for CC2 Reduced setpoint T° (1012) ...°C Reduced setpoint T°...
  • Page 98 STRATTON MK3 - Installation, Use and Maintenance OPTIMISATION page 2 / 4 Line No. Value • Menu Heating circuit (1 or 2 or 3) Daily ECO function for automatic comfort / reduced switch according to the difference between the set point and the outdoor temperature (Deactivated by default). See Navistem B3100 manual for CC1 Daily heating limit CC1 (732) 0 °C Daily heating limit CC2 (1032) 0 °C for CC2 Daily heating limit CC3 (1332)
  • Page 99 STRATTON MK3 - Installation, Use and Maintenance OPTIMISATION page 3 / 4 Time range setting path Short press Time and date User interface ..CC1 time program Mon. - Sun. “Preselection” 06:00 "1 phase ON" 22:00 "1 phase OFF" Line No. Value •...
  • Page 100 STRATTON MK3 - Installation, Use and Maintenance OPTIMISATION page 4 / 4 DHW CIRCUIT OPTIMISATION Line No. Value • DHW tank menu Start setpoint T° over-value (5020) 16 °C Adjust the over value • Configuration menu Installation frost protection (6120) Activate the heating circuits' frost protection mode Setting the anti-legionella cycle (if desired) •...
  • Page 101 • DHW tank menu Over-value of the boiler outlet temperature when the DHW is restarted Outlet setpoint T° raise (5020) 16 °C Adjustment on an Hamworthy Rubis W3000 or Rubis EVO W3100 preparation unit without a savings and performance kit: Parameters menu / DHW production / Main setpoint (C1): C1 setpoint: 62 °C Summary of the rules for DHW set point adjustment on the STRATTON MK3 Setpoint of consuming circuit 1 (1859) = setpoint C1 Rubis + 5°C = 67°C...
  • Page 102 • DHW tank menu Over-value of the boiler outlet temperature when the DHW is restarted Outlet setpoint T° raise (5020) 16 °C Adjustment on an Hamworthy Rubis W3000 or Rubis EVO W3100 preparation unit without a savings and performance kit: Parameters menu / DHW production / Main setpoint (C1): C1 setpoint: 58 °C Summary of the rules for DHW set point adjustment on the STRATTON MK3 Setpoint of consuming circuit 1 (1859) = setpoint C1 Rubis + 10°C = 68°C...
  • Page 103 STRATTON MK3 - Installation, Use and Maintenance BOILER PUMP NOT FROM THE KIT page 1 / 3 If you choose to install a pump you supply yourself, it can be On/Off or analogue controlled (0-10V) Case of a supplied pump controlled by an On/Off signal Connect the boiler directly to output Qx3 if consumption is <1A, otherwise use a relay to interface.
  • Page 104 STRATTON MK3 - Installation, Use and Maintenance BOILER PUMP NOT FROM THE KIT page 2 / 3 Case of a supplied pump controlled by a 0-10V signal Connect the pump power supply to terminals 13/14/15 if consumption is <1A, otherwise connect the power supply to the customer’s electrical cabinet. The kit (AGU2.551) should be purchased for implementing 0-10V signal control. To guarantee the temperature at the secondary, it is advisable to place a sensor after the mixing bottle, the kit reference and its implementation is described below. Option Secondary bottle sensor (B10) Control accessory required Quantity Device reference Order N°...
  • Page 105 STRATTON MK3 - Installation, Use and Maintenance BOILER PUMP NOT FROM THE KIT page 3 / 3 Use the following settings to determine the values of the previous section's parameters by respecting the data presented in the summary table of the flow rates below: Model (kW) Min. flow (l/min) 19.2 19.2 38.3 38.3 50.0 57.3 2322 (%) with our circulator kits Max. flow (l/min) 28.7 39.3 50.0 69.3...
  • Page 106: Spare Parts List

    STRATTON MK3 - Installation, Use and Maintenance 10. SPARE PARTS LIST 00U07446310-A Figure 32 - STRATTON MK3 casing 00U07428680-C 106 / 154...
  • Page 107 STRATTON MK3 - Installation, Use and Maintenance MODELS ITEM DESCRIPTION Front jacket 200313 200315 Complete user interface flap 78703 Blue front panel 200322 Power plug 200110 Wall fixing hook 200246 Concentric adaptor 200305 200306 Flue adaptater gasket D80/D100 interior 200307 200308 Front Jacket fasteners 200320 Front jacket complete fixing system 200321 06.02.2023 107 / 154...
  • Page 108 STRATTON MK3 - Installation, Use and Maintenance 00U07446060-A Figure 33 - Control panel 00U07428680-C 108 / 154...
  • Page 109 STRATTON MK3 - Installation, Use and Maintenance MODELS ITEM DESCRIPTION Fuse (T 6.3 H - 5x20) 71898 Plastic hatch 200140 LMS Mini 6.4 200122 200123 200127 200129 200131 200135 200136 Lanyard 200141 Adhesive seal 200142 Round fuse holder 200139 Switch 76134 LED board + LED ribbon cable + LED cover 200143 Selector 76135...
  • Page 110 STRATTON MK3 - Installation, Use and Maintenance 00U07446350-A Figure 34 - Body and burner for 70 kW models and lower 00U07428680-C 110 / 154...
  • Page 111 STRATTON MK3 - Installation, Use and Maintenance MODELS ITEM DESCRIPTION Heat exchanger 200157 200158 200159 Complete premix valve 200018 Venturi 200240 200241 Venturi measurement connection 200221 200222 Gas valve outlet elbow flange 200211 200212 G20 injector 200208 G31 injector 200249 Gas valve 200236 200291 Gas tube 200230 200231 200232...
  • Page 112 STRATTON MK3 - Installation, Use and Maintenance 321 322 00U07447310-A Figure 35 - Body and burner for 80 to 120 kW models 00U07428680-C 112 / 154...
  • Page 113 STRATTON MK3 - Installation, Use and Maintenance MODELS ITEM DESCRIPTION Air pressure switch 200014 Gas temperature sensor 200094 ZAG 1 ignition transformer 72131 EMC fan filter Premix trunk 200018 Premix valve seal 200088 Hydraulic clip (sachet) 76686 Flow tube 200099 Long bleed pipe 200108 Safety valve 6 bar M1/2’’ - F1/2’’ 200248 Plastic funnel M1/2 200247 Hydraulic collector (with sensors) 200092 Exchanger bottom refractory insulation 76470 Seal burner holder...
  • Page 114 STRATTON MK3 - Installation, Use and Maintenance 425 426 00U7444900-A Figure 36 - Body and burner for 150 kW model 00U07428680-C 114 / 154...
  • Page 115 STRATTON MK3 - Installation, Use and Maintenance MODEL ITEM DESCRIPTION Heat exchanger 200166 Gas temperature sensor 200094 ZAG 1 ignition transformer 72131 Air pressure switch 200014 EMC fan filter Premix trunk 200019 Premix valve seal 200089 Long bleed pipe 200108 1/4 female quick coupler 200091 Condensate siphon 78571 Hydraulic clip (sachet) 76686 Flow tube 200100 Pressure sensor and clip 200095...
  • Page 116: Customer Regulation Parameters Table

    STRATTON MK3 - Installation, Use and Maintenance 11. CUSTOMER REGULATION PARAMETERS TABLE Boiler: ..........site: ..........serial no: ..................Please transfer all parameter modifications into this document! Note: The "access" column indicates the level of accessibility to information for programming (U for end user, M for commissioning and S for specialist). The Commissioning accessibility level integrates the End User level. In the same way, the Specialist level integrates the Commissioning level.
  • Page 117 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 3rd period start time 3rd period stop time Default values Frost protection Timer programme 3: Heating circuit 3 Preselection Mon-Sun 1st period start time 06:00 1st period stop time 22:00 2nd period start time 2nd period stop time...
  • Page 118 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting End (dd.mm) Temperature level Frost protection Heating circuit 1 Ambient temperature comfort setpoint CC1 20 °C Reduced ambient temperature setpoint CC1 18 °C Ambient temperature frost protection setpoint CC1 10 °C Maximum comfort setpoint CC1 35 °C...
  • Page 119 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting Speed. regl. filtr. time const. 5 min T° level switching reduced Switching of heating circuit 1 protection mode Heating circuit 2 1010 Operation heating circuit 2 20 °C 1012 Ambient temperature comfort setpoint CC2...
  • Page 120 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting Heating circuit 3 1310 Ambient temperature comfort setpoint CCP 20 °C 1312 Reduced ambient temperature setpoint CCP 18 °C 1314 Ambient setpoint temp. frost protection CCP 10 °C 1316 Maximum comfort setpoint CCP...
  • Page 121 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 1630 DHW load priority none 1640 Anti-legionalla function stop 1641 Frequency of anti-legionella operation 1642 Anti-legionella operation Day Monday 1644 Time of anti-legionella operation 05:00 1645 Anti-legionella operation setpoint (1640) 55 °C 1646...
  • Page 122 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 2253 DHW supply pump timer stop 1 min 2270 Return temperature limitation 8 °C 2321 Rot. speed on start 100% 2322 Minimum boiler pump rotation speed 34 % 42 % 35 %...
  • Page 123 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 2503 Switching wait time 2550 Gas energy meter 2551 Gas meter correction 2560 Exhaust flap stop timer 30 s 2630 Auto drain function Stop 2655 Drain function activation time 10 s 2656 Drain cut-off duration...
  • Page 124 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 3870 Solar pump minimum rotation speed 3871 Solar pump maximum rotation speed 100% 3880 Antifreeze type none 3881 Antifreeze concentration 3884 Solar pump flow volume 200 l/h 3887 Pulse value for gain 10 l...
  • Page 125 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 5101 DHW pump minimum rotation speed 100% 5102 DHW pump maximum rotation speed 100% 5108 Load pump start rot. speed 100% DHW instantaneous water heater 5420 DHW flow setpoint over-value 10 °C 5444...
  • Page 126 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 5715 Heating circuit 2 stop 5721 Heating circuit 3 stop 5730 DHW sensor DHW B3 sensor 5731 DHW pump/valve Load pump 5732 Pump cut-off time if change CH to DHW 5733 Pump stop delay if change CH ->...
  • Page 127 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 6042 Module 2 BX21 sensor input none 6043 Module 2 BX22 sensor input none 6044 Module 3 BX21 sensor input none 6045 Module 3 BX22 sensor input none 6046 Function input H2/H21 mod.
  • Page 128 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 6253 Logic signal output UX21 module 3 standard 6254 Signal output UX21 module 3 6255 Output function UX22 module 3 none 6256 Logic signal output UX22 module 3 standard 6257 Signal output UX22 module 3...
  • Page 129 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 6835 Software diagnostic code 4 6840 History 5 00:00 6845 Software diagnostic code 5 6850 History 6 00:00 6855 Software diagnostic code 6 6860 History 7 00:00 6865 Software diagnostic code 7...
  • Page 130 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 7130 Chimney function 7131 Chimney function burner power 7140 Manual operation stop 7143 Regulator stop function 7145 Regulator stop setpoint 7146 Drain function 7147 Drain type 7170 Customer Service Centre 7250...
  • Page 131 STRATTON MK3 - Installation, Use and Maintenance Line Programming Access Default value Customer setting 8772 Modem ambient temperature CC2 Safety unit 9500 Pre-ventilation time 9504 Fan speed in pre-ventilation 4090 4220 4930 3100 100: 3100 120: 2900 150: 2690 9512 Fan rotation speed in charge of ignition 2430 3280...
  • Page 132: Option Kits

    STRATTON MK3 - Installation, Use and Maintenance 12. OPTION KITS 12.1.Boiler mounted kits 1. UIN 235347 VFC PUMP CONTROL 2. UIN 235342 BOILER RUN/FAULT SIGNALLING 3. UIN 235792 HC EXTENSION MODULE 4. UIN 235787 PWM TO 0-10V CONVERTER 5. UIN 235783 LPB INTERFACE 6. UIN 235791 MODBUS INTERFACE 12.2.External kits 7. UIN 235781 PROGRAMMABLE ROOM SENSOR 8. UIN 533901457 OUTDOOR TEMPERATURE SENSOR 9. UIN 235782 OFFSET ADJUSTABLE ROOM SENSOR 10. UIN 563605609 INSERTION TEMP. SENSOR AND POCKET 11. UIN 533901594 STRAP ON TEMP. SENSOR 12. UIN 235784 MERLEY SEQUENCER – ASSEMBLED 13. UIN 235785 MERLEY SEQUENCER – KIT 14. UIN 235788 HEATING CIRCUIT CONTROL – ASSEMBLED 15.
  • Page 133: Boiler Mounted Kits

    STRATTON MK3 - Installation, Use and Maintenance 12.1. Boiler mounted kits 12.1.1. UIN 235347 VFC PUMP CONTROL Refer to the relevant sections of the Boiler installation manual as required when carrying out the installation. The Pump control kit converts the demand signal from a 230V relay QXn output into a Volts Free enable signal for a circulating pump SELV Start/Stop input signal. 12.1.1.1. Kit contents 1. QXn Mains Lead 2. VFC Pump Enable Lead...
  • Page 134 STRATTON MK3 - Installation, Use and Maintenance 12.1.1.3. Pump wiring Note. Any of the QX1 to 3 230V relay outputs may be reconfigured as required for the installation. Wiring options: 1. Boiler pump. For a boiler pump the VFC pump control kit mains lead may be connected to QX2. This is the default setting for a boiler pump, no configuration is required. 2. DHW pump. For a DHW pump the VFC pump control kit mains lead may be connected to QX3. This is the default setting for a DHW pump or valve, no configuration is required. For a simple Constant temperature Heating circuit, QX1 may be reconfigured and the VFC pump control kit mains lead may be connected to QX1, but this 230V relay output will need to be configured. 12.1.1.4. Configuration for a Heating Circuit HC operation Line No.
  • Page 135 STRATTON MK3 - Installation, Use and Maintenance 12.1.2. UIN 235342 REMOTE SIGNALLING KIT FITTING INSTRUCTIONS Refer to the relevant sections of the Boiler installation manual as required when carrying out the installation. 12.1.2.1. Install the kit as follows: On the AGU2.550A109, make sure that the dip switches are set as j this is the default factory setting. • Attach the AGU 2.550A109 into the support holes between the electrical connections • Install the RAST5 plug into connection X1 • Install the multicoloured cable into connection X50...
  • Page 136 STRATTON MK3 - Installation, Use and Maintenance For VFC signals Contacts on X1 L (1) and QX21 (7) can be used for the following: Boiler flame on/Boiler demand (closed contact) Contacts on X1 L (1) and QX22 (5) can be used for the following: Fault errors (closed contact) E133 flame failure E110 temperature high limit E132 low gas pressure E132 flue or condensate blocked. For mains supply 230V signals, connect the white lead into X1 brown wire to L (1) and blue wire N (2). Connect the opposite end of the cable into terminal 17 live, and terminal 18 neutral, as shown. Contacts on X1 N (6) and QX21 (7) 230V can be used for the following: Boiler flame on/Boiler demand (closed contact) Contacts on N (4) and QX22 (5) 230V can be used for the following: Fault errors (closed contact) E133 flame failure E110 temperature high limit E132 low gas pressure E132 flue or condensate blocked.
  • Page 137 STRATTON MK3 - Installation, Use and Maintenance 12.1.4. UIN 235787 PWM TO 0-10V CONVERTER KIT FITTING INSTRUCTIONS Refer to the relevant sections of the Boiler installation manual as required when carrying out the installation. 12.1.4.1. Installation Install the kit as follows: On the AGU2.551A109, • Set slope 1 adjustment to full anticlockwise • Mode UX42 jumper should be left set to position b, it has no influence on the operation of channel 1 This is the default factory setting Attach the AGU 2.551A109 into a vacant clip-in space into the support holes between the electrical connections, only 2 clip-in devices or one clip-in and a VFC pump control relay may be fitted at any one time. Externally mounted option kits are available if required.
  • Page 138 STRATTON MK3 - Installation, Use and Maintenance Install the multicoloured cable into connection X50 Make the following connection using the cable supplied, between the Boiler PELV installer connections and the Clip-in module X2 plug. Boiler connector AGU2.551 X2 Pin 5, M 12.1.4.3. Pump wiring Pin 6, PI41 Make the following connections between the AGU2.551 and the external pump 0-10V analogue input connections. 00U07428680-C 138 / 154...
  • Page 139 STRATTON MK3 - Installation, Use and Maintenance 12.1.4.4. Slope 1 Settings The adjustment of the slope for the relationship between the PWM input and the 0-10V DC output can be adjusted as shown in the graph below. Pump connector AGU2.551 X2 Pin 1, M 0-10V control Pin 2, UX41 12.1.5. UIN 235783 LPB Interface Refer to the Boiler installation manual as required when carrying out the installation. This option kit enables communication over the LPB (Local Process Bus) between a boiler and another external LPB device, boiler or External module.
  • Page 140: External Kits

    STRATTON MK3 - Installation, Use and Maintenance 12.1.5.2. Fixing 1. Remove the two left hand side cables, 14-way ribbon cable and 2 core cable 2. Remove the mounting screws from the control box and keep them 3. Fit the Ribbon cable into the OCI345, check the orientation 4. Remove the 2-way RAST5 connector from the OCI345 5. Secure the OCI345 to the control box using the two mounting screws 6. Strip the outer sheath of the 2-core cable 7. Strip the two inner conductors and crimp on ferrules 8. Secure the cables: DB Brown MB White 9. Plug the RAST5 connector back into the OCI345, note that the connector is polarised and so the screw heads face towards the control box 12.1.5.3. Wiring For cascade operation, connect each LPB bus connection in daisy chain: DB to DB, MB to MB, etc.
  • Page 141 STRATTON MK3 - Installation, Use and Maintenance 12.2.1. UIN 235781 Programmable Room Sensor Refer to the QAA74 installation instructions, and the Boiler or External module installation manual as required when carrying out the installation. 12.2.1.1. Location Determine the optimum location as recommended in the QAA74 installation instructions. For basic operation a 2-core cable is only required to be run between the Room Sensor and the associated Boiler or External module.
  • Page 142 STRATTON MK3 - Installation, Use and Maintenance Determine the optimum location, on a North or North West facing external wall, as recommended in the QAC34 installation instructions. For operation a 2-core cable is only required to be run between the Outside Sensor and the associated Boiler or External module. Note: In an electrically noisy environment, it is recommended that a screened cable be used. The screen should only be connected to ground at one end. 12.2.2.2.
  • Page 143 STRATTON MK3 - Installation, Use and Maintenance 12.2.3. UIN 235782 Offset Adjustable Room Sensorr Refer to the QAA55 installation instructions, and the Boiler or External module installation manual as required when carrying out the installation. 12.2.3.1. Location Determine the optimum location as recommended in the QAA55 installation instructions. For operation a 2-core cable is only required to be run between the Room Sensor and the associated Boiler or External module.
  • Page 144 STRATTON MK3 - Installation, Use and Maintenance 12.2.4.1. Application The Insertion Temperature Sensor can be used for several applications where a temperature measurement for system operation is required. Common examples are: a. Cascade – Common flow sensor, B10 b. DHW tank sensor, B3 c. DHW outlet flow sensor, B38 d. Heating circuit flow temperature sensor, B1 B12 B14 12.2.4.2. Location Determine the optimum location for the sensor pocket and fit. If additional cable length is required, a 2-core cable is only required to be run between the Insertion Temperature Sensor and the associated Boiler or External module. Use an appropriate electrical connection box, securely mounted, in which to make the connection between the sensor cable and the...
  • Page 145 STRATTON MK3 - Installation, Use and Maintenance For an external module refer to the installation documentation provided with the specific option kit. 12.2.4.7. Configuration Line No. Parameter Settings 5931 Sensor input BX2 As required 5932 Sensor input BX3 As required DHW sensor B3/B38 As required: 5730 DHW sensor sensor B3/Thermostat/ DHW outlet sensor B38 As required: 5131 Comparison temperature transfer DHW sensor B3/DHW outlet sensor B38...
  • Page 146 STRATTON MK3 - Installation, Use and Maintenance 12.2.5.4. Sensor cable size Cross-sectional area Maximum length 0.25 mm 20 m 0.5 mm 40 m 1.0 mm 80 m 1.5 mm 120 m 12.2.5.5. Fixing Follow the fixing instructions as detailed on the box. 12.2.5.6. Wiring At the Boiler end make the connections as required. Signal Boiler B3/B38 For an external module refer to the installation documentation provided with the specific option kit.
  • Page 147 STRATTON MK3 - Installation, Use and Maintenance 13. APPENDIX A Product data ≤ 70 kW Product reference Trade mark Hamworthy Model Code 82635 82636 82637 Nominal power Prated 39.0 54.0 68.0 Seasonal energy efficiency class Classe Seasonal energy efficiency η...
  • Page 148: Installation, Commissioning & Service Record Log Book

    STRATTON MK3 - Installation, Use and Maintenance 14. INSTALLATION, COMMISSIONING & SERVICE RECORD LOG BOOK Your log book IMPORTANT Failure to install & commission this appliance to the manufacturer’s instructions may invalidate the warranty. This does not affect your statutory rights. The use of this Log is to enable the safety features of this boiler to be proven; a principle that is enshrined in health and safety law and endorsed by the Building Regulations, Health &...
  • Page 149 STRATTON MK3 - Installation, Use and Maintenance 06.02.2023 149 / 154...
  • Page 150 STRATTON MK3 - Installation, Use and Maintenance 00U07428680-C 150 / 154...
  • Page 151 STRATTON MK3 - Installation, Use and Maintenance 06.02.2023 151 / 154...
  • Page 152 STRATTON MK3 - Installation, Use and Maintenance 00U07428680-C 152 / 154...
  • Page 153 STRATTON MK3 - Installation, Use and Maintenance 06.02.2023 153 / 154...
  • Page 154 01202 662555 Customer Service Centre Hamworthy Heating Limited, Wessex House, New Fields Business Park, Stinford Road, Poole, Dorset BH17 0NF Telephone: 01202 662500 Fax: 01202 662522 Email: aftersales@hamworthy-heating.com Website: www.hamworthy-heating.com Hamworthy reserves the right to make changes and improvements which may necessitate alteration to the specification without prior notice.

This manual is also suitable for:

S3-40S3-60S3-70S3-80S3-100S3-120 ... Show all

Table of Contents

Save PDF