12.1.2. UIN 235342 REMOTE SIGNALLING KIT FITTING INSTRUCTIONS
12.1.2.1.
Install the kit as follows:
06.02.2023
Refer to the relevant sections of the Boiler installation manual as required
when carrying out the installation.
On the AGU2.550A109, make sure that the dip switches are set as j
this is the default factory setting.
• Attach the AGU 2.550A109 into the support holes between the electrical
connections
• Install the RAST5 plug into connection X1
• Install the multicoloured cable into connection X50
STRATTON MK3 - Installation, Use and Maintenance