ETC Installation Guide
ALCR-DIN
4. Terminate the normal sense wiring leads to the normal lighting and
control device for the area controlled.
a. Connect the Normal Power Sense and the Normal Control
(Switch) Sense wires to the provided screw terminals.
b. Connect the Normal Neutral Sense to the provided screw
terminal.
5. If you are connecting to 0–10 VDC or fluorescent lighting loads,
connect to the terminals labeled 0–10 V/ FLO. See
on page 9
6. Are you are installing a remote triggering device to remotely
activate the emergency circuit?
• No: Go to
• Yes: See
7. Restore power to the circuits.
Remote Activation Input
The ALCR-DIN offers a normally closed, dry contact input to
accommodate connection to a fire alarm panel, security system, or test
switch. This input ships from the factory with a blue wire loop (jumper)
connected to two of the top screw terminals. It is a complete loop that
disables remote activation. Do not remove or cut this jumper unless you
are installing a remote triggering device.
Note:
before connecting to a remote device. See
The remote device that triggers the Emergency circuit On must provide a
normally closed, maintained dry contact closure for fire alarm systems.
When the remote device is activated, the contact closure opens and the
contacts force the ALCR-DIN into the emergency On state.
Note:
system must be installed within 305 m (1,000 ft) of the Automatic
Load Control Relay when using recommended 1 mm
wire.
1. Remove the wire loop jumper from the Remote Loop In and Remote
Loop Out terminals.
ALCR-DIN
i.
Note:
To ensure that the emergency lighting connected to
the device turns On in the event of a power loss, you must
connect the Normal Power Sense wires upstream of any
switched control device for the normal lighting loads.
for more information.
Initial Test on page 7
Remote Activation Input below
ETC recommends that you power up and test your system
The remote triggering device, test switch, or emergency
to confirm the connection.
Page 5 of 12
Examples of Use
for wiring instructions.
Initial Test on
page 7.