ETC Installation Guide
ALCR-DIN
Examples of Use
Note:
for clarity of the example installation scenario.
Switch Control Arrangement
• When normal power is present, the switch controls both the normal
and emergency light fixtures.
• When the normal power is lost, when the [Push to Test] button is
pressed, or when the remote activation input is activated (opened),
the emergency fixture turns On full regardless of the switch state.
Normal Neutral (White)
Normal Power Sense (Black)
Emergency Power In (Black)
Emergency Neutral (Gray)
Backup Arrangement
• When normal power is present, the emergency fixture is turned Off.
• When the normal power is lost, when the [Push to Test] button is
pressed, or when the remote activation input is activated (opened),
the emergency fixture turns On full.
Normal Neutral (White)
Normal Power Sense (Black)
Emergency Power In (Black)
Emergency Neutral (Gray)
ALCR-DIN
In the following diagrams, unused wire pairs are omitted
Switch
ALCR
ALCR-DIN
Normal Control (Red)
Emergency Power Out (Red)
Emergency Power Out (Red)
Page 9 of 12
Normal Fixture
Emergency
Fixture
Emergency
Fixture
ETC