ETC ALCR-DIN Installation Manual page 6

Hide thumbs Also See for ALCR-DIN:
Table of Contents

Advertisement

ETC Installation Guide
ALCR-DIN
2. Connect the Remote Loop In and Remote Loop Out terminals on the
ALCR-DIN to the single pole contacts on the remote device or test
switch.
3. Go to
Configure a Time Delay
If your lighting requires a warmup period (for example, for high-intensity
discharge [HID] lamps), you can configure a time delay to keep the
emergency lighting on for a period of time after the normal power is
restored. The default time delay is zero. To configure a longer transition
time follow the steps below.
1. Press the [Option] button on the ALCR-DIN. Both the Status and
Remote LEDs will blink to indicate the current time delay
configured.
2.
Press and release the
[Option] button to cycle
through the settings, and
stop when the blink pattern
matches the setting you
want.
3.
Wait 10 seconds for the
ALCR-DIN to save the setting
and resume normal
operation.
Note:
senses the loss of normal power and switches to the emergency
state and when the emergency state has been triggered by the
remote activation input.
ALCR-DIN
Remote Activation Test on page 8
The configured time delay applies when the ALCR-DIN
No. of Blinks
1 blink
2 blinks
3 blinks
4 blinks
5 blinks
Page 6 of 12
to confirm the connection.
Time Delay
no delay
(default)
10 seconds
30 seconds
10 minutes
15 minutes
ETC

Advertisement

Table of Contents
loading