Connecting Power - Siemens SIMATIC NET RUGGEDCOM RS930L Installation Manual

Hide thumbs Also See for SIMATIC NET RUGGEDCOM RS930L:
Table of Contents

Advertisement

Installing the Device
2.5 Connecting Power
2.5

Connecting Power

The RUGGEDCOM RS930L supports power input from a single high AC/DC or low DC
power supply.
Note
10
1
2
3
Normally Closed
1
Common
2
Normally Open
3
Figure 2.4
Failsafe Alarm Relay Wiring
For 110/230 VAC rated equipment, an appropriately rated AC circuit breaker
must be installed.
For 125/250 VDC rated equipment, an appropriately rated DC circuit breaker
must be installed.
Use minimum #16 gage copper wiring when connecting terminal blocks.
Equipment must be installed according to applicable local wiring codes and
standards.
All line-to-ground transient energy is shunted to the Surge Ground terminal. In
cases where users require the inputs to be isolated from ground, remove the
ground braid between Surge and Chassis Ground. Note that all line-to-ground
transient protection circuitry will be disabled.
RUGGEDCOM RS930L
Installation Manual, 11/2022, C79000-G8976-1034-11