Table 22 Usage Of Cables For Connecting Enclosures - Fujitsu ETERNUS DX100 S4 Site Planning Manual

Hybrid storage systems
Hide thumbs Also See for ETERNUS DX100 S4:
Table of Contents

Advertisement

2.
Rack Installation Specifications
Rack Installation Requirements
Cable Connection (Between Enclosures)
Reverse cabling can be used to connect enclosures in the ETERNUS DX when the ETERNUS DX is configured with
two controllers. For reverse cabling, the length of the provided cable between controller 1 (CM#1) and the last
drive enclosure (connection destination) may not be enough. Longer cables may also be required according to
the installation locations of enclosures that are used in the same rack or the installation locations of enclosures
that are used in multiple racks.
The cable lengths that are required between enclosures should be taken into consideration when enclosure in-
stallation locations are being determined.
For 2U drive enclosures (2.5" type and 3.5" type), the length of the provided cables between enclosures is
0.75m.
For 4U drive enclosures (high-density drive enclosures), the length of the provided cables between enclosures is
2.5m.
For extended connections, 2.5m, 3.5m, 6.0m, 15m, and 30m cables are available.
Cables with a length of 0.75m, 2.5m, 3.5m, and 6.0m are Mini SAS HD copper cables, and cables with a length of
15m and 30m are Mini SAS HD active optical cables. There are no operational issues even if different types of
cables exist in the ETERNUS DX.
The following guideline shows how the mini SAS HD cables between enclosures should be used according to
their cable length.

Table 22 Usage of Cables for Connecting Enclosures

Cable length
0.75m
2.5m
3.5m
6.0m
15m
30m
FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide
Usage
Provided with 2U drive enclosures and used for connecting 2U drive enclosures.
Provided with 4U drive enclosures. These cables can also be used as extension cables when the
lengths of the provided cables are insufficient.
These cables are used for the following purposes:
Connection between 4U drive enclosures
Connection between 2U and 4U drive enclosures
Reverse cabling when two or more 2U drive enclosures are installed
Used as extension cables for connections between the racks.
Used as extension cables when the connection length between the racks is more than 3.5m.
Used as extension cables when the connection length between the racks is more than 6.0m.
Used as extension cables when the connection length between the racks is more than 15.0m.
Copyright 2021 FUJITSU LIMITED
47
P3AM-7632-18ENZ0