Rack Installation Requirements
Power Distribution Units (2U, 16 Outlets, 16A)
When connecting, keep the current capacity totaling the current consumption value of power cords that con-
nect to outlets OUT1 to OUT8 within 16A for each power distribution unit.
When connecting, keep the current capacity totaling the current consumption value of power cords that con-
nect to outlets OUT1 to OUT4 and the current capacity totaling the current consumption value of power cords
that connect to outlets OUT5 to OUT8 within 8A for each power distribution unit.
When connecting a new enclosure, if the current capacity totaling the current consumption value of power
cords that connect to outlets OUT1 to OUT4 exceeds 8A, connect to OUT5.
When the current capacity totaling the current consumption value of power cords that connect to outlets OUT5
to OUT8 exceeds 8A, connect to the next power distribution unit.
Power Distribution Units (2U, 12 Outlets, 16A)
When connecting, keep the current capacity totaling the current consumption value of power cords that con-
nect to outlets OUT1 to OUT6 within 16A for each power distribution unit.
When connecting, keep the current capacity totaling the current consumption value of power cords that con-
nect to outlets OUT1 to OUT3 and the current capacity totaling the current consumption value of power cords
that connect to outlets OUT4 to OUT6 within 8A for each power distribution unit.
When connecting a new enclosure, if the current capacity totaling the current consumption value of power
cords that connect to outlets OUT1 to OUT3 exceeds 8A, connect to OUT4.
When the current capacity totaling the current consumption value of power cords that connect to outlets OUT4
to OUT6 exceeds 8A, connect to the next power distribution unit.
For details on the current consumption of each power cord for each type of enclosure, refer to
Specifications" (page
FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide
29).
Copyright 2021 FUJITSU LIMITED
46
"Outlet/Socket
P3AM-7632-18ENZ0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eternus dx200 s4Eternus dx100 s3Eternus dx200 s3

Table of Contents