Fujitsu ETERNUS DX100 S4 Site Planning Manual

Fujitsu ETERNUS DX100 S4 Site Planning Manual

Hybrid storage systems
Hide thumbs Also See for ETERNUS DX100 S4:
Table of Contents

Advertisement

Quick Links

P3AM-7632-18ENZ0
FUJITSU Storage
ETERNUS DX100 S4/DX200 S4,
ETERNUS DX100 S3/DX200 S3
Hybrid Storage Systems
Site Planning Guide
Requirements for transportation/installation

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu ETERNUS DX100 S4

  • Page 1 P3AM-7632-18ENZ0 FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Requirements for transportation/installation...
  • Page 2: Table Of Contents

    Rack Installation Requirements ....................43 Placement in the Rack ............................43 Cable Connection ..............................44 Installable Racks ........................... 54 Fujitsu Racks .................................54 Non-Fujitsu Racks ..............................54 FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 3 Connection Example 5 (Connections When 2U and 4U DEs Are Used Together in the Same Rack) ...52 Figure 30 Connection Example 6 (Connections in Multiple Racks) ................53 Figure 31 Unit Installation Area ..........................55 FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 4 Cable Lengths When Connecting Each Enclosure to the Power Distribution Unit........44 Table 22 Usage of Cables for Connecting Enclosures....................47 Table 23 Specifications for the Unit Installation Area .....................55 FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 5 Preface Fujitsu would like to thank you for purchasing the FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 (hereinafter collectively referred to as ETERNUS DX). The ETERNUS DX is designed to be connected to Fujitsu servers (Fujitsu SPARC Servers, PRIMEQUEST, PRIMERGY, and other servers) or non-Fujitsu servers.
  • Page 6 - Do not use alcohol or other solvents to clean the ETERNUS storage system. Warning layout ribbon FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 7: Eternus Dx Installation

    2U (*4) (3.0kg) ´ 2 (*6) Power Voltage AC 100 – 120V, AC 200 – 240V Phase Single Frequency 50Hz/60Hz FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 8 3.5" type 4.0m /min Drive enclosure 2.5" type 4.0m /min 3.5" type 4.0m /min High-density type 12.0m /min FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 9 *8: These values are measured when a single controller enclosure and a single drive enclosure are configured in an environment in which the temperature is 23 ± 2°C at 0 meters above sea level. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED...
  • Page 10: Eternus Dx100 S3

    2U (*4) (3.0kg) ´ 2 (*6) Power Voltage AC 100 – 120V, AC 200 – 240V Phase Single Frequency 50Hz/60Hz FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 11 3.5" type 4.0m /min Drive enclosure 2.5" type 4.0m /min 3.5" type 4.0m /min High-density type 12.0m /min FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 12 *8: These values are measured when a single controller enclosure and a single drive enclosure are configured in an environment in which the temperature is 23 ± 2°C at 0 meters above sea level. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED...
  • Page 13: Eternus Dx200 S4

    AC 200 – 240V 340W (350VA) High-density type AC 100 – 120V 1,300W (1,320VA) AC 200 – 240V 1,300W (1,320VA) FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 14 Vibration limit Operating 400gal Not operating 1,000gal Noise emission Sound pressure level 49dB (A) (*8) Sound power level 6.7B FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 15: Table 5 Efficiency And Power Factor Of The Power Supply Unit (Eternus Dx200 S4)

    GOLD certified power supply units are used. 80PLUS is a power saving program for electrical ® equipment promoted by the 80PLUS program. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 16: Eternus Dx200 S3

    AC 200 – 240V 340W (350VA) High-density type AC 100 – 120V 1,300W (1,320VA) AC 200 – 240V 1,300W (1,320VA) FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 17 Vibration limit Operating 400gal Not operating 1,000gal Noise emission Sound pressure level 49dB (A) (*8) Sound power level 6.7B FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 18 *8: These values are measured when a single controller enclosure and a single drive enclosure are configured in an environment in which the temperature is 23 ± 2°C at 0 meters above sea level. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED...
  • Page 19: Storage System Dimensions

    The dimension values do not include any protruding parts (approximation). Figure 1 2.5" Type Controller Enclosure Dimensions 482mm Side Front FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 20: Figure 2 3.5" Type Controller Enclosure Dimensions

    The dimension values do not include any protruding parts (approximation). Figure 2 3.5" Type Controller Enclosure Dimensions Side 482mm Front FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 21: Figure 3 2.5" Type Drive Enclosure Dimensions

    The dimension values do not include any protruding parts (approximation). Figure 3 2.5" Type Drive Enclosure Dimensions Side 482mm Front FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 22: Figure 4 3.5" Type Drive Enclosure Dimensions

    The dimension values do not include any protruding parts (approximation). Figure 4 3.5" Type Drive Enclosure Dimensions Side 482mm Front FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 23: Figure 5 High-Density Drive Enclosure Dimensions

    The dimension values do not include any protruding parts (approximation). Figure 5 High-Density Drive Enclosure Dimensions Side 482mm Front FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 24: Compliance Standards

    WEEE-compliant (waste electrical and electronic equipment) Power conversion efficiency • ® 80PLUS GOLD *1: The target ETERNUS DX is the ETERNUS DX100 S4/DX200 S4. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 25: Package Size

    *5: These values are for product ID ETFP16U-L / ETFP12U-L. *6: These values are for product ID ETFP48U-L / ETFP32U-L. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED...
  • Page 26: Installation Area

    Rear service area 850mm or more ETERNUS DX 1000mm Front service area or more 500mm or more 1800mm or more FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 27: Figure 8 Installation And Service Areas (When A High-Density Drive Enclosure Is Installed_2)

    Figure 9 Service Area (When a High-Density Drive Enclosure Is Installed in the Top Part of the Rack) Service area above 500mm or more the rack Rack: front FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 28: Installation Environment

    Estimate the amount of heat in the exhaust air from the ETERNUS DX by using the heat generation amount and exhaust air amount that are listed in "Installation Specifications" (page FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 29: Installation Methods

    If any of the power supply lines fails, all of the necessary power is supplied from the other power sources. The necessary power can be supplied even when two power supply units fail. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED...
  • Page 30: Specifications For Optional Power Supply Products

    IEC60320 C14G IEC60320 C13 1.5m 250V 10A tween the ETERNUS DX and the socket (IEC60320 C13 n IEC60320 C14G) FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 31: Table 10 Specifications For Ac200V Power Cords (For Regions Other Than The Emeia, Central American, And Carib- Bean Regions)

    Rating: 250V 10A tween the ETERNUS DX 1.0m (Normal usage rating: and the socket 1.5m (IEC60320 C13 n 3.0m IEC60320 C14) FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 32: Figure 10 Power Distribution Units (Ac8A/200-240V, 1U, 4 Outlets, 2 Inlets)

    Plug type Cable length (Socket) (Socket) IEC60320 C13 NEMA L6-30P NEMA L6-30R 4.4m Rating: 250V 30A (Normal usage rating: 24A) FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 33: Figure 12 Power Distribution Units (2U)

    Plug type Cable length (Socket) (Socket) IEC60320 C13 NEMA L6-30P NEMA L6-30R 4.0m Rating: 250V 30A (Normal usage rating: 24A) FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 34: Figure 13 Power Distribution Units (2U)

    Plug type Cable length (Socket) (Socket) IEC60320 C13 NEMA L6-30P NEMA L6-30R 4.0m Rating: 250V 30A (Normal usage rating: 24A) FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 35: Required Number Of Outlets/Sockets

    Power distribution unit (AC24A/200-240V, 1U, 4 outlets) ETERNUS DX (without power distribution units) AC 100 – 120V AC 200 – 240V FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 36: Figure 14 Breaking Characteristics Of Distribution Board Circuit Protectors

    1.5 2 5 6 7 8 10 15 20 30 40 50 80 100 Current (ratio for the current rating) FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 37: Figure 15 Example Of A Power Supply Connection When A Power Distribution Unit (1U) Is Used

    Distribution board board ↓ To power supply facility ↓ To power supply facility PSU: Power Supply Unit Circuit Protector FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 38: Figure 16 Example Of A Power Supply Connection When A Power Distribution Unit (2U) Is Used

    Distribution board board ↓ To power supply facility ↓ To power supply facility PSU: Power Supply Unit Circuit Protector FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 39 Power distribution unit Line 0 Line 1 Distribution Distribution board board p To power supply facility p To power supply facility FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 40: Figure 17 Example Of A Power Supply Connection When A Power Distribution Unit Is Not Used

    Line 0 Line 1 PSU: Power Supply Unit Circuit Protector Only connect the ETERNUS DX to circuit protectors. • FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 41: Input Power Supply Lines

    Figure 19 Dual-Line Power Supply (When Connecting to a UPS Unit) Power distribution unit ETERNUS DX Line 1 Line 0 FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 42: Figure 20 Single-Line Power Supply (When Connecting To Power Sockets)

    Power distribution unit ETERNUS DX Power distribution unit Drive enclosure Drive enclosure Line 0 Line 1 Controller enclosure FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 43: Rack Installation Specifications

    If drive enclosures are to be added in the future, securing sufficient space for power distribution units in the bottom of the rack is recommended. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED...
  • Page 44: Cable Connection

    The distance between the enclosure and the power distribution unit in this example is 6U, which is calculated by subtracting the PDU in location 1 from the DE in location 7. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED...
  • Page 45: Figure 24 Ac Cable Connection

    When the current capacity totaling the current consumption value of power cords that connect to outlets OUT5 to OUT8 exceeds 12A, connect to the next power distribution unit. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED...
  • Page 46 For details on the current consumption of each power cord for each type of enclosure, refer to "Outlet/Socket Specifications" (page 29). FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 47: Table 22 Usage Of Cables For Connecting Enclosures

    Used as extension cables when the connection length between the racks is more than 6.0m. Used as extension cables when the connection length between the racks is more than 15.0m. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED...
  • Page 48: Figure 25 Connection Example 1 (2U De Connections In The Same Rack)

    DE#06 (2U) DE#05 (2U) DE#04 (2U) DE#03 (2U) DE#02 (2U) DE#01 (2U) Cables that are supplied as standard 0.75m FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 49: Figure 26 Connection Example 2 (Connections In Multiple Racks)

    DE#01 (2U) DE#08 (2U) DE#07 (2U) Extension cables 3.5m/6.0m/15m/30m Connections in the same rack are omitted in the above figure. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 50: Figure 27 Connection Example 3 (2U De Connections In The Same Rack)

    DE#05 (2U) DE#04 (2U) DE#03 (2U) DE#02 (2U) DE#01 (2U) Cables that are supplied as standard 0.75m Extension cables 2.5m FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 51: Figure 28 Connection Example 4 (4U De Connections In The Same Rack)

    Figure 28 Connection Example 4 (4U DE Connections in the Same Rack) DE#04 (4U) DE#03 (4U) DE#02 (4U) DE#01 (4U) Cables that are supplied as standard 2.5m FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 52: Figure 29 Connection Example 5 (Connections When 2U And 4U Des Are Used Together In The Same Rack)

    DE#04 (2U) DE#03 (2U) DE#02 (4U) DE#01 (4U) Cables that are supplied as standard 0.75m 2.5m Extension cables 2.5m FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 53: Figure 30 Connection Example 6 (Connections In Multiple Racks)

    DE#01 (2U) DE#08 (2U) DE#07 (2U) Extension cables 3.5m/6.0m/15m/30m Connections in the same rack are omitted in the above figure. FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 54: Installable Racks

    This section explains the racks in which the ETERNUS DX can be installed. Fujitsu Racks The ETERNUS DX can be installed in a Fujitsu 19-inch rack. For information about whether the ETERNUS DX can be installed in an EOLed rack or not, contact your sales representative.
  • Page 55: Figure 31 Unit Installation Area

    Make sure to perform the installation according to the placement requirements described in "Installation Specifi- cations" (page 7) "Installation Environment" (page 28). FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide Copyright 2021 FUJITSU LIMITED P3AM-7632-18ENZ0...
  • Page 56 However, Fujitsu shall assume no responsibility for any operational problems as the result of errors, omissions, or the use of information in this manual. Fujitsu assumes no liability for damages to third party copyrights or other rights arising from the use of any information •...

This manual is also suitable for:

Eternus dx200 s4Eternus dx100 s3Eternus dx200 s3