1.
ETERNUS DX Installation
Installation Specifications
Item
Maximum heat
generation
(*7)
Maximum amount
of exhaust air
Environmental con-
ditions
Vibration limit
Noise emission
(*8)
FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Site Planning Guide
Controller enclosure 2.5" type
3.5" type
Drive enclosure
2.5" type
3.5" type
High-density type
Controller enclosure
Drive enclosure
Temperature
Temperature gradient
Humidity
Humidity gradient
Maximum wet bulb temperature
Altitude above sea level
Airborne dust
Gas concentration tolerance level
Oil vapor
Seawater (salt corrosion)
Operating
Not operating
Sound pressure level
Sound power level
Copyright 2021 FUJITSU LIMITED
ETERNUS DX200 S3
AC 100 – 120V
3,000kJ/h
AC 200 – 240V
3,000kJ/h
AC 100 – 120V
2,700kJ/h
AC 200 – 240V
2,700kJ/h
AC 100 – 120V
1,600kJ/h
AC 200 – 240V
1,600kJ/h
AC 100 – 120V
1,300kJ/h
AC 200 – 240V
1,300kJ/h
AC 100 – 120V
4,700kJ/h
AC 200 – 240V
4,700kJ/h
2.5" type
4.0m
3.5" type
4.0m
2.5" type
4.0m
3.5" type
4.0m
High-density type
12.0m
Operating
10 – 40°C
Not operating
0 – 50°C
Shipping
-40 – 60°C
15°C/Hr or less
Operating
20 – 80%RH
Not operating
8 – 80%RH
Shipping
8 – 90%RH
30%/day or less
29°C
0 – 3,000m
0.15mg/m
Cl
SO
NH
NO
HCl: 6.6ppb or less, HF: 3.6ppb or less
0.2mg/m
If the ETERNUS DX is installed on the ocean
or premises within 0.5km from the coast,
necessary measures must be taken to pre-
vent salt corrosion.
400gal
1,000gal
49dB (A)
6.7B
17
3
/min
3
/min
3
/min
3
/min
3
/min
3
or less
: 6.8ppb or less, H
S: 7.1ppb or less,
2
2
: 37ppb or less,
2
: 423.5ppb or less,
3
: 52ppb or less, O
: 5ppb or less,
2
3
3
or less