Martindale Electric EASYPAT 2100 Instructions

Martindale Electric EASYPAT 2100 Instructions

Pat tester

Advertisement

Quick Links

INSTRUCTIONS
EASYPAT 2100
MARTINDALE
E L E C T R I C
Trusted by professionals

CONTENTS

1
Introduction
1.1
Description
1.2
Earth / Continuity (8A and 25A)
1.3
Earth / Continuity (200mA)
1.4
Insulation
1.5
1.6
Run Leakage
1.7
1.8
Unpacking & Inspection
1.9
Spares & Accessories
2
2.1
2.2
2.3
3
Operation
3.1
Earth Continuity (8A and 25A)
3.2
Earth Continuity (200mA)
3.3
Insulation
3.4
Run
3.5
Flash
3.6
Lead Test
4
4.1
4.2
Calibration
4.3
Repair & Service
4.4
Storage Conditions
4.5
Warranty
PAT TESTER
SAFETY INFORMATION: Always read before proceeding.

WARNING

These instructions contain information and warnings that are necessary for
safe operation and maintenance of the EasyPat. It is recommended that you
read the instructions carefully and ensure the contents are understood.
Failure to understand the instructions and comply with warnings and
instructions herein can result in serious injury, damage or even death.
In order to avoid the danger of electrical shock, it is important that proper
safety measures are taken when working with voltages exceeding 30V AC
rms, 42V AC peak or 60V DC. Never exceed the maximum allowable input
level for each function and range. Refer to the specifications for maximum
inputs. Never touch exposed wiring, connections or live circuits.
The EasyPat must only be used in conditions and for the purpose which it
has been constructed. Attention should be paid to safety instructions,
technical specifications and use of the EasyPat in dry surroundings.
Always inspect your meter, test leads and accessories for any sign of
damage before use. If any abnormal conditions exist (e.g: broken test leads,
cracked case, display not reading, etc.), do not attempt to use it. Do not
expose it to direct sunlight, excessive temperature or moisture.
Keep these instructions for future reference. Updated instructions and
product information are available at: www.martindale-electric.co.uk.

SYMBOLS:

Equipment complies with relevant EU Directives
AC (Alternating Current)
Ground
Direct Current
Equipment protected by Double Insulation (Class II)
Caution - refer to accompanying documents
Caution - risk of electric shock
2
1. INTRODUCTION
1.1 Description
The Martindale EasyPat is an LCD indicating portable appliance tester, which is
housed in a rugged injection moulded case with a removable lid. The base of the
case contains the complete power and electronic circuitry. Basic safety
instructions are presented on the inside of the lid, and a pannier bag, which
provides storage for the flash gun, supply adaptors and comprehensive instruction
manual, clips onto the top of the lid.
Operation of the Martindale EasyPat is straightforward. The five main tests,
continuity, insulation, run current, run leakage and flash, provided by this
instrument are selected by depressing one of five push-button switches on the
front panel. A three position rocker switch selects a test current of 200mA DC, 8A
AC or 25A AC for the continuity test. While the key is depressed the relevant
measurement is displayed on the large, custom LCD Display.
The Martindale EasyPat allows fast, simple testing on all tools, appliances and IT
equipment in accordance with the recommendations of the Electricity At Work Act,
the Health And Safety Executive and the Electronic And Business Equipment
Association. It should be noted that Class I equipment is earthed whereas Class II
equipment is not earthed (double-insulated), usually denoted by the symbol
3
4
Fig. 1
Over Temperature Indicator
.

Advertisement

loading

Summary of Contents for Martindale Electric EASYPAT 2100

  • Page 1 Keep these instructions for future reference. Updated instructions and product information are available at: www.martindale-electric.co.uk. SYMBOLS: Equipment complies with relevant EU Directives AC (Alternating Current) Ground EASYPAT 2100 PAT TESTER Direct Current Equipment protected by Double Insulation (Class II) MARTINDALE Caution - refer to accompanying documents...
  • Page 2 It is important that the wander earth lead is plugged into the front results in a fail no further tests should be carried out on the appliance until the panel of the EasyPat 2100 whenever the EasyPat is in use. fault in its protective earthing has been rectified.
  • Page 3 It is important that the wander earth lead is plugged cause a rapid increase in the temperature within the instrument. into the front panel of the EasyPat 2100 whenever the EasyPat is in use. A thermal trip has been incorporated into the instrument to protect against over Connect the EasyPat 2100 to a suitable supply.
  • Page 4 Alternatively, a chargeable collection and return service is available. 4.3 Repair & Service There are no user serviceable parts in this unit. Return to Martindale Electric Company Ltd if faulty, unless fuse replacement only is necessary. Our service department will promptly quote to repair any faults that occur outside the warranty period.
  • Page 5 Martindale Electric Company Limited Metrohm House, Imperial Park, Imperial Way, Watford, Hertfordshire, WD24 4PP, UK Tel: +44(0)1923 441717 Fax: +44 (0)1923 446900 E-mail: sales@martindale-electric.co.uk Website: www.martindale-electric.co.uk © 2016 Martindale Electric Company Ltd. Registered in England No. 3387451. E. & O.E. Rev2...