Installation and User Guide

Sub-menu (H1-H4)

The structure in this Sub-menu is navigated like the main menu .
Sensor type:
to select correct type and
Be aware that 2 sensors must be used for each heater circuit (H1-H4) and that these must
be the same type .
-PT1000
-NTC16K (NTC16 .8K)
-NTC100 (NTC100K)
-NTC2K
-NTC5K
-NTC10K
-NTC15K (Std . DEVI sensor)
Has no default value as this must be set in setup wizard . Please refer to the sensors maximum
and minimum temperatures to ensure safe operation of the system .
Setpoint:
Settable with
Settable temperature setpoint (desired maintained temperature) between 20 .0-80 .0°C
(20-60 .0°C on plastic pipe) .
Has no default value as this must be set in setup wizard .
Hysteresis:
Settable with
Settable between 1 .0-10 .0K
Defaults to 2 .0K
High temperature:
Settable with
Settable between 20 .0-90 .0K
Defaults to Setpoint+Hysteresis+5K
Not settable below setpoint
12
DEVIreg™ Hotwater
to confirm .
to select and
to select and
to select and
to confirm .
to confirm .
to confirm .