Menu survey

Function
Normal display
Shows the temperature at the selected
sensor
Define view in O17
If you wish to see selected defrost stop
temperature, give the lower button a brief
push (1 sec.)
no= stop on temperature not selected
Thermostat
Differential
Max. limitation of thermostat's setting
temperature
Min. limitation of thermostat's setting
temperature
Temperature unit (°C/°F)
Correction of signal from S4 (S
)
out
Correction of signal from S3 (S
)
in
Start/Stop of refrigeration
Reference displacement during night opera-
tion
Define thermostat function
1=ON/OFF, 2=Modulating
Definition and weighting, if applicable, of
thermostat sensors
100%=S4 (S
), 0%=S3 (S
).
out
in
The thermostat temperature can be seen
in U17
Time between melt periods
Duration of melt periods
Alarm
Alarm time delay
Door alarm time delay
Time delay during cooling
High alarm limit
Low alarm limit
Compressor
Min. ON-time
Min. OFF-time
Defrost
Defrost stop temperature
Interval between defrost starts
Max. defrost duration
Time displacement of defrost cut-ins during
start-up
Drip-off time
Fan start delay after defrost
Fan start temperature
Fan cut-in during defrost (yes/no)
Defrost sensor
0=S4 (S
) , 1=S5 (S
), 2=non. Stop on time
out
def
Defrost at power up
RTC module (if installed)
see RTC instructions
Injection control function
Max. value of superheat reference
Min. value of superheat reference
MOP temperature
AKV valve's time period
Should only be changed to OFF by trained
staff
Adaptive control
Should only be changed to OFF by trained
staff
Average opening degree
Should only be changed by trained staff
EKC 414A
Para
Factory
Min.
Max.
meter
settings
-
°C
-
°C
r01
0.1 K
10.0 K
2.0
r02
-49°C
50°C
50.0
r03
-50°C
49°C
-50.0
r05
°C
°F
0/°C
r09
-10.0 K
10.0 K
0.0
r10
-10.0 K
10.0 K
0.0
r12
OFF
ON
OFF
r13
-20.0 K
20.0 K
0.0
r14
1
2
1
r15
0%
100%
100
r16
0 h
10 h
1
r17
0 min
10 min.
5
A03
0 min.
120 min 30
A04
0 min.
90 min.
60
A12
0 min.
240 min 120
A13
-50°C
50°C
5.0
A14
-50°C
50°C
-30.0
c01
0 min
50 min
0.0
c02
0 min
50 min
0.0
d02
0
25°C
6.0
d03
OFF
48 h
8
d04
0
180 min 45
d05
0
240 min 0
d06
0
60 min
0
d07
0
60 min
0
d08
-15
0°C
-5.0
d09
no
yes
no
d10
0
2
2
d13
no
yes
no
t01 to
t16
n09
3.0 K
15.0 K
12.0
n10
3.0 K
10.0 K
3.0
n11
-50.0°C
15°C/off 15°C
n13
3 sec.
6 sec.
6
n14
OFF
ON
on
n16
10%
75%
30.0
Manual RS8CK502 © Danfoss 05-2005
Start-up time for signal reliability
Should only be changed by trained staff.
Stability factor for superheat control.
Changes should only be made by trained
staff
Forced closing.. AKV valve shut in pos. ON
Fan
Fan stop on compressor cut out
Delayed fan stop when compressor is cut out F02
Safety function. The fan stops if the S5 tem-
perature reaches this value
Miscellaneous
Delay of output signal after start-up
Define digital input signal (DI:
OFF=not used, 1=Door alarm, 2=defrost
start, 3=Night operation, 4=External start/
stop, 5 = Coordinated defrost with cable
connections
Network address (range = 0-60)
ON/OFF switch (service-pin message)
Access code
Used sensor type for S3, S4 and S5 (Pt / PTC)
Set supply voltage frequency
Define digitalt output signal (DO:
0=not used
Coordinated defrost with cable connections:
1=Master, 2= Slave
Max. standby time after coordinated defrost
Display S4 % (S
)
out
0%=S3 (S
)
in
100%=S4 (S
)
out
Manual control of outputs:
OFF=No override
1: Compressor reay is ON
2: Defrost relay is ON
3: Fan relay is ON
4: Alarm relay is OFF
5: DO output is ON
6: AKV output is ON
7: Light relay is ON
When manual control is terminated, the set-
ting must be changed to OFF
Pressure transmitter working range – min.
value
Pressure transmitter working range – max.
value
Inject-ON definition
When the ON input is cut out refrigeration
is stopped.
Here you define how the fan relay and the
alarm function are to act:
1 = Fan relay = ON, alarm monitoring active
2 = Fan relay = OFF, alarm monitoring active
3 = Fan relay = OFF, no alarm monitoring
4 = Fan relay = ON, no alarm monitoring
5 to 8= as 1 to 4, but without connection to
terminal 40-41.
Refrigerant setting
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717.
6=R13. 7=R13b1. 8=R23. 9=R500.
10=R503. 11=R114. 12=R142b. 13=User
defined. 14=R32. 15=R227. 16=R401A.
17=R507. 18=R402A. 19=R404A. 20=R407C.
21=R407A. 22=R407B. 23=R410A. 24=R170.
25=R290. 26=R600. 27=R600a. 28=R744.
29=R1270. 30=R417A
SW: 1.1x
n17
5%
70%
30.0
n18
0
10
4
n36
OFF
ON
OFF
F01
no
yes
no
0 min
30 min
0
F04
-50.0
50.0/off 50.0
o01
0 sec.
600 sec
5
o02
OFF
5
0
o03
0
990
0
o04
OFF
ON
OFF
o05
OFF
100
OFF
o06
Pt
Ptc
0/Pt
o12
50 Hz
60 Hz
50
o13
0
2
0
o16
1 min
30 min
20
o17
0%
100%
100
o18
OFF
7
OFF
020
-1 bar
5 bar
-1
021
6 bar
36 bar
12
o29
1
8
5
o30
0
30
0
15