2.3 Setup on the Programmable Controller (GX Works3) Side

2.3 Setup on the Programmable Controller (GX Works3) Side

This section explains how to set up parameters for IO-Link master SC-LG2-CEF-P.
The parameter setting method differs according to the master station unit.
The parameter setting method is explained below, using Mitsubishi Electric Corporation's
RJ71EN71 as an example.
Reference
For details, refer to the instruction manual of the master station unit that you use.
● Example of RJ71EN71(CCIEF) unit parameter settings
Station type: Master station
Network No.: 1
<Network configuration settings>
Station number: 1
RX / RY settings (starting / ending): 1000 / 106F
RWw / RWr settings (starting / ending): 1000 / 1083
<Refresh settings>
Link side
Device
Starting
name
address
SB
00000
SW
00000
RX
01000
RY
01000
RWr
01000
RWw
01000
2-4
Ending
address
001FF
001FF
0106F
0106F
01083
01083
CPU side
Device
Starting
name
address
SB
00000
SW
00000
X
01000
Y
01000
W
01400
W
00400
WUME-SCLGCT-3