ZIEHL-ABEGG RH Series Assembly Instructions Manual

ZIEHL-ABEGG RH Series Assembly Instructions Manual

Radial impellers and plug fans directly powered with iec standard motor

Advertisement

Quick Links

english
RH../ER../GR..
Radial impellers RH.. and plug fans ER../GR.. directly powered with
IEC standard motor
Assembly instructions
Keep for reference!
L-BAL-F018-GB 2021/22 Index 004
Part.-No. 00282063-GB

Advertisement

Table of Contents
loading

Summary of Contents for ZIEHL-ABEGG RH Series

  • Page 1 english RH../ER../GR.. Radial impellers RH.. and plug fans ER../GR.. directly powered with IEC standard motor Assembly instructions Keep for reference! L-BAL-F018-GB 2021/22 Index 004 Part.-No. 00282063-GB...
  • Page 2: Table Of Contents

    Assembly instructions RH../ER../GR.. Content General notes ..........Scope of documentation .
  • Page 3 Assembly instructions RH../ER../GR.. Electrical installation ........Safety precautions .
  • Page 4: General Notes

    Assembly instructions RH../ER../GR.. General notes 1 General notes Compliance with the following instructions is mandatory to ensure the functionality and safety of the product. If the following instructions given especially but not limited for general safety, transport, storage, mounting, operating conditions, start-up, mainte- nance, repair, cleaning and disposal / recycling are not observed, the product may not operate safely and may cause a hazard to the life and limb of users and third parties.
  • Page 5: Exclusion Of Liability

    We do not accept any liability for possible errors or omissions in the information con- tained in data, illustrations or drawings provided. ZIEHL-ABEGG SE is not liable for damage due to misuse, improper use or as a consequence of unauthorized repairs or modifications.
  • Page 6 Safety • The conveyance of solid matter or solids content in the conveying medium is not permissible and can lead to dangerous situations. ZIEHL-ABEGG rejects any liability for damage of any kind as a result of such use. • Only operate the fans in the permissible temperature ranges (see order acknowledge- ment).
  • Page 7: Intended Use

    Assembly instructions RH../ER../GR.. Safety 2.2 Intended use Attention! • The fans are only intended for the conveyance of air or mixtures similar to air. • Any other use above and beyond this is considered not for the intended purpose unless agreed otherwise by contract. The manufacturer will not be liable for any damage resulting from this.
  • Page 8: Explanations Of Symbols

    Assembly instructions RH../ER../GR.. Safety 2.4 Explanations of symbols Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows. Attention! General hazardous area. Death or severe injury or significant property damage can occur if the corresponding precautions are not taken! Danger due to electric current Danger by dangerous, electric voltage! Death or severe injury can occur if the corresponding precautions are not taken!
  • Page 9: Work On The Device

    ZIEHL-ABEGG.These parts were specifically designed for the device. There is no guarantee that parts from non-original sources are designed and manufactured in correspondence with load and safety requirements. Parts and optional equipment not supplied by ZIEHL-ABEGG are not approved by ZIEHL-ABEGG for use. L-BAL-F018-GB 2021/22 Index 004 Part.-No.
  • Page 10: Operator's Obligation Of Diligence

    The fans may not be operated until they are installed in line with their intended use. The supplied and certified guard grille of ZIEHL-ABEGG SE fans is designed in accordance with DIN EN ISO 13857 Table 4 (from the age of 14 up). In the event of deviations, further structural protective measures must be taken for safe operation.
  • Page 11: Note On The Erp Directive

    Product overview 3.2 Note on the ErP directive ZIEHL-ABEGG SE wishes to point out that, based on the directive (EU) no. 327/2011 of the Commission of 30th of March 2011 for enforcing directive 2009/125/EC (hereinafter referred to as ErP directive), the operational area of certain fans within the EU is bound by certain prerequisites.
  • Page 12: Disposal / Recycling

    Assembly instructions RH../ER../GR.. Product overview • Store the fan / motor in the original packaging in a dry area protected from the weather and protect it from dirt and weather until final installation. • Avoid prolonged storage; we recommend a maximum of one year (consult the manufacturer before starting if stored for longer).
  • Page 13: Mounting

    Assembly instructions RH../ER../GR.. Mounting 4 Mounting 4.1 General notes Attention! • Mounting is only to be undertaken by trained service personnel. The system manufacturer or the machine builder and/or the user is responsible that the inherent installation and security information are harmonized with the valid standard and guidelines (EN ISO12100 / 13857).
  • Page 14: Erecting The Equipment Design Er, Gr

    The assignment of the spacing dimensions of the damping elements can be taken from the catalogues on our home page under www.ziehl-abegg.de in the section Download - Ventilation and Control Engineering. •...
  • Page 15 Assembly instructions RH../ER../GR.. Mounting Attention! • ER.. plug fans may only be operated in installation position H (fan upright, motor shaft horizontal). • Connect all contact points securely to the foundation or plant. If not fastened sufficiently, there is a risk of the fan tipping over or coming loose - danger of injury! •...
  • Page 16: Mounting Rh

    Assembly instructions RH../ER../GR.. Mounting 4.3 Mounting RH Attention! Whenever working on a fan, under no circumstances loosen the bolts that hold the impeller to the hub! Impeller and hub together form a balanced module which may only be removed and fitted as a complete unit. Loosening these bolts can lead to imbalance and therefore to vibrations, even if the bolts are tightened correctly before restarting the fan! Impellers with fixed hub:...
  • Page 17 Assembly instructions RH../ER../GR.. Mounting Impellers with clamping bush hub: • The impeller is fitted to the end of the motor shaft using bushings. • Mounting: Clean and grease all bare surfaces (fitting surfaces of clamping sleeves and motor shaft). Insert clamping sleeve (1) into the hub (2) and line up the holes as shown in the fig.
  • Page 18: Installation And Usage Information

    Assembly instructions RH../ER../GR.. Mounting 4.4 Installation and usage information 4.4.1 Optimal installation distances according to for RH../ ER../ GR.. fans • Impeller blade external-diameter : Ø DSa • Distance on suction side: LA ≥ 0.5 x DSa * • Distance on pressure side: LD for C/Cpro ≥ 1 x DSa, LD for ZAbluefin ≥ 0.8 x DSa •...
  • Page 19 Assembly instructions RH../ER../GR.. Mounting • Changes to the flow direction before the fan create significant turbulence in the intake area. • Intake side “1” ≥ 1.0 x DSA, with guide blades this can be reduced to “1” 0.7 x DSA, otherwise there are increased acoustics and power loss.
  • Page 20: Possible Sources Of Faults During Installation

    Assembly instructions RH../ER../GR.. Mounting 4.4.3 Possible sources of faults during installation Please pay attention to possible sources of faults: • 90° change in flow direction and reduction in cross-section “5”. • Obstructions on the pressure side (long lamp, fluorescent lamp) “2”. •...
  • Page 21: Electrical Installation

    Assembly instructions RH../ER../GR.. Electrical installation 5 Electrical installation 5.1 Safety precautions Danger due to electric current • Work on electric components may only be carried out by trained electricians or by persons instructed in electricity under the supervision of an electrician in accordance with electrical engineering regulations.
  • Page 22: Frequency Inverter And Emc

    • When operating on the inverter harmful bearing currents can occur in the motor. This depends on many factors which, in many cases, ZIEHL-ABEGG cannot influence. Thus, it comes down to the expert installation in the respective assembly situation. The following points serve as a guideline, but cannot always prevent bearing currents from occurring.
  • Page 23: Operation With Frequency Inverter

    During operation of the frequency inverter pay attention to the following points: • In order to approve its centrifugal fans with standard motors, ZIEHL-ABEGG carries out extensive qualification tests. Depending on the installation conditions and the other system components in use (e.g. frequency inverter incl. parameter configura- tion), in individual cases there may be unusual noises and vibrations (resonance) caused by the electrics.
  • Page 24: Motor Protection

    Caution! Thermostatic switches switch on again automatically after cooling. The constructor of the plant must ensure that the fan does not start up automatically, or that an automatic start-up does not result in any hazard. ZIEHL-ABEGG motor contactors prevent an automatic restart after the drive has cooled.
  • Page 25: Start-Up

    3. A-rated sound power levels of over 80 dB(A) are possible, see product catalogue. 4. Fans from ZIEHL-ABEGG SE are delivered balanced in accordance with DIN ISO 21940-11 for the appropriate fan category in accordance with ISO 14694 Check the fan for mechanical vibrations after installation. If the limit values of the...
  • Page 26: Trouble Shooting

    Assembly instructions RH../ER../GR.. Trouble shooting 7 Trouble shooting 7.1 Code of behaviour in the event of faults In the event of faults, which represent a danger to people, installation or environment, " the fan must be switched off. Search for the cause of the error. "...
  • Page 27 Check wings/blades for damage, soiling or ice see "Impeller blocked or dirty" Unusual noises Ball bearing damaged / Replacement of the ball bearing by ZIEHL-ABEGG re- worn quired Impeller / blade scrapes / When indicated, clear foreign bodies/dirt from the fan brushes see "Impeller blocked or dirty"...
  • Page 28: Service Work

    Check the impeller, in particular the weld-seams, for possible cracks. • Repair, e.g. by welding is prohibited! • Bolted-on wheels and/or wings may only be replaced by authorised ZIEHL-ABEGG SE staff. The manufacturer shall not be liable for damage caused through improper repair work. •...
  • Page 29: Cleaning

    Assembly instructions RH../ER../GR.. Service work Information • Maintenance should be carried out based on VDMA 24186-1. The scope and frequency of maintenance must be determined depending on operating and installation conditions. Maintenance work on the motor must be carried out according to the motor manufacturer's specifications.
  • Page 30: Enclosure

    Assembly instructions RH../ER../GR.. Enclosure 9 Enclosure 9.1 Technical data Line voltage see Fan-rating plate Fans are rated for S1 continuous operation. Switching frequency Controls must not allow extreme switching operation! -20 ...40 °C or according to rating plate Permissible temperature range Please see the technical documentation of the product for the minimum operation and maximum ambient temperature valid for the respective fan ;...
  • Page 31: Ec Declaration Of Incorporation

    Electronically commutated internal or external rotor motor (also with integrated EC controller) complies with the requirements in Appendix I, Articles 1.1.2, 1.1.5, 1.4.1, 1.5.1 in EC Machinery Directive 2006/42/EC. The manufacturer is ZIEHL-ABEGG SE Heinz-Ziehl-Strasse D-74653 Künzelsau The following harmonised standards have been used: EN 60204-1:2018 Safety of machinery;...
  • Page 32 It is prohibited to commission this incomplete machine until it has been secured that the machine into which it was incorporated complies with the stipulations of the EC Machinery Directive. Künzelsau, 17.05.2021 (location, date of issue) ZIEHL-ABEGG SE ZIEHL-ABEGG SE Dr. W. Angelis Dr. D. Kappel Head of Technics Ventilation Technology...
  • Page 33: Index

    Assembly instructions RH../ER../GR.. 9.3 Index Assembly ignitable atmosphere Imbalance impeller Ball bearing bearing lifting beam linevoltage capacitor clamping bush hub cleaning process overheating protection cold greasing equipment condensation water drains overmodulation holes construction contact points protective devices cooling Removal damping elements resonance range direction arrow direction of rotation...
  • Page 34: Manufacturer Reference

    9.4 Manufacturer reference Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact: ZIEHL-ABEGG SE Heinz-Ziehl-Straße 74653 Künzelsau phone: +49 (0) 7940 16-0 info@ziehl-abegg.de...

This manual is also suitable for:

Er seriesGr series