Piping Installation; Preparing Refrigerant Piping; Refrigerant Piping Requirements; Refrigerant Piping Insulation - Daikin FXHA32AVEB8 Installation And Operation Manual

Vrv system air conditioner
Hide thumbs Also See for FXHA32AVEB8:
Table of Contents

Advertisement

a
b
a
Air outlet
b
Plastic water container with tube length ≥100 mm
13

Piping installation

13.1

Preparing refrigerant piping

13.1.1

Refrigerant piping requirements

CAUTION
Piping MUST be installed according to instructions given in
"13  Piping
installation"  [ 4   19]. Only mechanical joints (e.g.
braze+flare connections) that are compliant with the latest
version of ISO14903 can be used.
NOTICE
The piping and other pressure-containing parts shall be
suitable for refrigerant. Use phosphoric acid deoxidised
seamless copper for refrigerant piping.
▪ Foreign materials inside pipes (including oils for fabrication) must
be ≤30 mg/10 m.
Refrigerant piping diameter
For piping connections of the indoor unit, use the following piping
diameters:
Class
Liquid pipe
32
50+63
100
Refrigerant piping material
▪ Piping material: phosphoric acid deoxidised seamless copper
▪ Flare connections: Only use annealed material.
▪ Piping temper grade and thickness:
Outer diameter
Temper grade
(Ø)
6.4 mm (1/4")
Annealed (O)
9.5 mm (3/8")
12.7 mm (1/2")
15.9 mm (5/8")
(a)
Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.
FXHA-A
VRV system air conditioner
3P668115-5E – 2022.11
(mm)
Pipe outer diameter (mm)
Gas pipe
Ø6.4
Ø9.5
Ø6.4
Ø12.7
Ø9.5
Ø15.9
(a)
Thickness (t)
Ø
≥0.8 mm
13.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035
and 0.045 kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Pipe outer diameter
)
p
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
15.9 mm (5/8")
Ø
Ø
i
i
Ø
Ø
p
p
t
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20  mm to prevent condensation on the surface of the
insulation.
13.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING
13.2.1
To connect the refrigerant piping to the
indoor unit
CAUTION
Install the refrigerant piping or components in a position
where they are unlikely to be exposed to any substance
which may corrode components containing refrigerant,
unless the components are constructed of materials that
are inherently resistant to corrosion or are suitably
protected against corrosion.
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
Refrigerant piping can be connected from following directions:
t
b
a
Rear right piping
b
Right piping
c
Upward piping
Rear right piping
1 Remove the rear piping pipe port cover and cut out the holes for
piping. When cutting out the holes, make sure to avoid the knob
part of the cover.
13 Piping installation
Insulation inner
Insulation thickness
diameter (Ø
)
i
8~10 mm
≥10 mm
12~15 mm
≥13 mm
14~16 mm
≥13 mm
17~20 mm
≥13 mm
c
a
Installation and operation manual
(t)
19