▪ Remove the decoration side covers (right, left). Remove the
fixing screw from both side covers, pull the decoration panel to the
front and remove the accessories.
a
b
c
a
Accessories
b
Fixing screw for side covers
c
Decoration side cover
To mount the indoor unit
1 Open the knockout hole at the wiring inlet at the rear or the top
of the unit, and install the resin bushing (accessory).
a
Resin bushing (accessory)
b
Knockout hole (for leading in from the top)
c
Knockout hole (for leading in from the rear)
2 Remove the hanger bracket. Loosen the 2 hanger bracket
installation bolts (M8) on both sides (total 4 places) within
10  mm. Remove the fixing screw (M5) from the rear hanger
bracket and pull the hanger bracket backward in the direction of
the arrow in order to remove it.
b
a
10 mm
b
b
c
a
Hanger bracket fixing screw (M5)
b
Hanger bracket installation bolt (M8)
c
Hanger bracket
d
Indoor unit
CAUTION
Do NOT remove the (milky white) tape from the exterior of
the indoor unit. Removing the tape may cause an electric
shock or a fire.
3 Fix
the
hanger
bracket
"12.2.1 Guidelines when installing the indoor
4 Lift up the indoor unit and slide it to the back. Fix the hanger
bracket installation bolt (M8) for temporary hanging. Do NOT
hold the unit by the reinforcing plate.
FXHA-A
VRV system air conditioner
3P668115-5E – 2022.11
a
b
c
a
d
c
to
the
suspension
bolts.
unit" [ 4  16].
b
c
d
a
Hanger bracket
b
Hanger bracket installation bolt (M8)
c
Hanger bracket fixing screw (M5)
d
Reinforcing plate
5 Install the hanger bracket fixing screws (M5) on both sides back
(2 screws in total).
6 Fully tighten all hanger bracket installation bolts (M8) (4 screws
in total).
7 Make sure the unit is level. Refer to
installing the indoor
unit" [ 4  16].
12.2.2
Guidelines when installing the drain
piping
Make sure condensation water can be evacuated properly. This
involves:
▪ General guidelines
▪ Connecting the drain piping to the indoor unit
▪ Checking for water leaks
General guidelines
▪ Pipe length. Keep drain piping as short as possible.
▪ Pipe size. Keep the pipe size equal to or greater than that of the
connecting pipe (vinyl pipe of 20  mm nominal diameter and
26 mm outer diameter).
▪ Slope. Make sure the drain piping slopes down (at least 1/100) to
prevent air from being trapped in the piping. Use hanging bars as
shown.
1~1.5 m
a
Hanging bar
Allowed
Not allowed
▪ Condensation. Take measures against condensation. Insulate
the complete drain piping in the building.
▪ Combining drain pipes. You can combine drain pipes. Make
sure to use drain pipes and T-joints with the correct gauge for the
operating capacity of the units.
a
T-joint
To connect the drain piping to the indoor unit
NOTICE
Incorrect connection of the drain hose might cause leaks,
and damage the installation space and surroundings.
Drain piping can be connected from following directions:
12 Unit installation
a
b
"12.2.1  Guidelines when
a
(mm)
a
Installation and operation manual
17