Gas pressure regulator with controller
Table of Contents

Advertisement

Assembling the regu-
lator unit
Next task
HON 380 gas pressure regulator with HON 673/674 controller
Figure
Proceed in the reverse order as for the disassembly in "Performing maintenance
on the regulator unit". See above.
Depending on what you want to do next, proceed as indicated in the relevant sec-
tion:
 Installing the regulator unit (see page 61)
 Completing the maintenance (see page 63)
Step
Description
18
IMPORTANT! Pull out the quad ring
(1) upwards so as to avoid damaging
the sliding surface of the intermedi-
ate piece.
Replace the quad ring (1) with a new,
greased quad ring.
19
Turn the intermediate piece and re-
lease the locking ring (1) to remove
the plain bearing (2).
Check the plain bearing for damage.
Replace it if necessary.
Replace the O-ring (3) with a new, lu-
bricated O-ring.