Honeywell HON 380 User And Maintenance Instructions page 29

Gas pressure regulator with controller
Table of Contents

Advertisement

Installing the gas
pressure regulator
Final inspection
Next task
HON 380 gas pressure regulator with HON 673/674 controller
Proceed as follows:
Figure
Conduct a final inspection to check whether the following criteria are met:
 All screwed connections on the device and supply lines are securely fas-
tened.
If ...
at least one criterion is not met
all criteria are met
Proceed as follows:
Installing the device connections (see page 30)
Transport and installation
Step
Description
1
Remove the transport panels.
2
Transport the device to the location
where it will be installed.
 The device needs to be installed in
the piping in a horizontal and level
position. If you want to use a differ-
ent installation position, consult
with the manufacturer first.
 Pay attention to the direction of
flow for the gaseous fluid as
marked on the body.
3
Secure and support the device's posi-
tion in such a way that the device can
be installed in the piping without any
stress and that the piping's weight will
be supported as well.
4
Install the flange gaskets.
5
Screw down the flange crosswise in
the specified order. When doing so,
make sure to observe the torques
specified by the flange gaskets' man-
ufacturer.
then ...
you should correct the error before proceed-
ing with the next task.
you may proceed with the next task.
29