Essential Settings - ABB Advant Controller 80 User Manual

Table of Contents

Advertisement

Essential Settings

AC 80 User's Manual
Only the user-adjustable settings are represented. (The tables also
include the information readable from the output terminals.) For more
details, see the AC 80 PC Elements Reference Manual.
MVICHAN
Base part:
NAME
Max. 20 characters
ACT
0 = Spare element
1 = Active element
NET
Network number of MVI channel.
NODE
Individual node number of MVI channel.
MASTER
MVI channel in slave (0) or master (1) mode.
TIMESYNC
Time synchronisation:
NONE; MASTER; SLAVE
MVINODE
NAME
Max. 20 characters
ACT
0 = Spare element
1 = Active element
NET
MVI network number.
REMNODE
Remote node number.
In Master mode: node number of Slave
In Slave mode: node number of Master
MVB
NAME
Max. 12 characters
ACT
0 = Spare element
1 = Active element
REGADDR
Register start address in external PLC/RTU.
In RCOM: MVB identifier.
CMDCODE
Command code to be executed by the MVI protocol
handler (protocol-dependent).
AUXINFO1
Auxiliary information 1 (protocol-dependent).
AUXINFO2
Auxiliary information 2 (protocol-dependent).
NO_BREC
Number of Boolean records DAT(B).
NO_INT
Number of integer records DAT(I).
NO_INTL
Number of long integer records DAT(IL).
NO_REAL
Number of real records DAT(R).
SOURCE
Source. Defines the direction of the data transmission
(RECEIVE; SEND).
4-27