ABB Advant Controller 80 User Manual page 32

Table of Contents

Advertisement

Chapter 2 – AC 80 Hardware and Connections
IBM Type 6A,
Belden 1215
TC505/
TC506
S1 S2 GND
TC501V150
IBM Type 1,
Belden 9182
2-18
First Station
min.
2 m
min.
0.1 m
BLUE
max. cable length 750 m
max. 32 stations
Figure 2-10 AF 100 bus connection diagram.
When connecting the station to the AF 100 twisted pair bus cable, the
incoming and outgoing cables can be connected either directly to the
terminal header or to a TC505/TC506 connection unit.
The minimum distance between stations is 4 metres. If the stations are
located inside the same cabinet, the minimum distance can be shorter
if the total bus length does not exceed 10 metres.
The TC501V150 is a termination unit for twisted pair cable (150 ohms).
Last Station
Terminal
Header
BLUE
S1 S2 GND
TC501V150
AC 80 User's Manual