Standard Control Functions; Freezing Protection During Cooling Process Or Dry Operation - Hitachi UTOPIA RAS-4HVRP2E Service Manual

Hide thumbs Also See for UTOPIA RAS-4HVRP2E:
Table of Contents

Advertisement

5 Control System

Standard control functions

5.6 Standard control functions

5.6.1 Freezing protection during cooling process or dry operation

Cooling or dry
operation
IU: Indoor unit
103
SMGB0136 rev.0 - 07/2021
Power supply
Is
No
compressor
operated for more than
*1)
30min.
*1)
?
: The check interval differs
depending on the conditions
Yes
Gas
or liquid
pipe surface
temperature on heat
exchanger
Lower than 0ºC
Is
it
continuous for
more than 3 min.?
Yes
MIF operation at set fan speed
(in case of dry operation.
MIF operation: OFF for 6 min.)
For individual
operation
IU electronic expansion valve:
completely closed
Is
it
continuous for more
than 3 min.? (6 min in case
of dry operation)
Yes
a
Gas or
liquid pipe surface
temp of indoor heat
exchanger
Higher than 14ºC
15
Yes
min
progress
No
Either
No
of pipe surface
temp
*2)
> 2ºC
*2)
: Pipe surface temperature
Yes
NOT adpopted at
Cooling or dry
operation
Higher than 0ºC
No
For simultaneous or
single operation
Inverter frequency = 0 Hz
No
Lower than 14ºC
a
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents