Wind Guard Wsp-264 - Hitachi UTOPIA RAS-4HVRP2E Service Manual

Hide thumbs Also See for UTOPIA RAS-4HVRP2E:
Table of Contents

Advertisement

2 Optional parts and installation
Optional parts and installation for RAS-3HVRC2

2.1.2 Wind guard WSP-264


Specifications
Material
Color
Weight
Unit fixing
screw
Accessories
Wind guard
fixing screw
Installation restriction

Installation
1 Attach the air flow guide to the air discharge grille with four (4) screws (supplied).
2 The fixing holes are located at 4 positions on the grille. (Screw tightening torque 2.4 - 3.1 N.m)
3 Do not remove the air discharge grille for air flow guide installation.
!
C A U T I O N
If the air guide is installed without discharge grille it may cause injury due to rotating fan.

One wind guard cover installation
Air discharge grille
202
Wind guard

Service space (In case of upward air discharge)
•  In case of right and left sides air discharge enough space for air 
discharge is required.
•  The downward air discharge is also available. In such case install the 
base under the unit to secure enough space for air discharge.
•  In case of serial units installation air discharge should be upward.
29
SMGB0136 rev.0 - 07/2021
Galvanized sheet metal + baked painting
UTOPIA Beige (Mussel code: 2.5Y8/2)
4.0 kg
4 x [M5 (SUS) x 30]
10 x [M5 (SUS) x 12]
Installation manual
"Guard net" "Air flow guide" or "Snow 
protection hood" is not available to install 
with Wind guard
1
4-6x10 Long Hole
2
5 (Both Sides) - M5 Screw (attachement)
4 x M5 fixing screw 
(Accessories)
1
2
2
Min.150 mm